Owner / Applicant Information
Jim Wolfe
University of Southern Indiana
8600 UNIVERSITY BLVD
EVANSVILLE IN 47712
Phone 8124914120
Email JWOLFE2@USI.EDU
Submitter Information
Roger Lehman
RLehman Consulting
1220 N Red Bank Rd
Evansville IN  
Phone 8125890331
Email rlehmanconsulting@gmail.com
Project Information
USI Arena Ph II PAC Remodel
8600 University BLVD
Evansville IN 47712
County VANDERBURGH
Project Type New   Addition   Alteration Y Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order? No No
Violation Issued by: NA
Local Building Official
Phone: 8124367868 Email: rbeane@evansville.in.gov
Local Fire Official 
Phone: 8124367868 Email: jbulger@usi.edu

Variance Details
Code Name: 12-4-12 Existing Buildings; Additions or Alterations
2014 IBC Table 601 footnote b
Conditions: A small 7'wide walkway less than 20' below roof deck divides 2 sections of the roof structure at the main beam. Main beam will be treated with 1 hr. fire protective spray on insulation, but bar joists in entire roof will not. 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or we
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: Entire existing 30000 sq. ft. 2 level PAC gymnasium facility is being upgraded from IIB  construction to IIA and being completely retrofitted with NFPA 13 sprinkler system throughout.  In the area where the small walkway crosses the building, upright sprinklers will be added within 12" of the roof deck on both sides of main beam and within 24" of each roof girder truss to  protect the roof system.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty) because  of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty) because  of major operational problems in the use of the building or structure.
Y
Y Imposition of the rule would result in an undue hardship (unusual difficulty) because  of excessive costs of additional or altered construction elements.
  Imposition of the rule would prevent the preservation of an architecturally or a historically significant part of the building or structure.
Facts: This building built in the early 70's would require fire protection to be sprayed on over the  entire 3 wood gym floors causing loss of use the facilities for practices and PE classes. Damage  to the wood floors is a risk.
The cost of sprinkling the entire building is very high and adding potentially six figure cost to  have the fire proofing completed is not justifiable considering the added protection provided by the sprinkler system.