Project Information
Muncie Water Treatment Plant - Phase 2 Improvements
1420 South Burlington Drive
Muncie IN 47302
County DELAWARE
Project Type New Y Addition   Alteration   Existing   Change of Occupancy  
Project Status U F=Filed U or Null=Unfiled
IDHS Issued Correction order?    
Violation Issued by: NA
Local Building Official
Phone: 7657474862 Email: [email protected]
Local Fire Official 
7657474862 Email: [email protected]
Phone:


Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC 903.2.5.1
Conditions: Sprinklers will not be provided in the chemical storage and treatment building which is  classified as H-2 (Activated carbon is a weakly explosive combustible dust. See attached  data sheet for additional information), H-3 (Oxidizers), H-4 (Corrosives)occupancies and F-2 (Water Treatment and Building Support areas).

 
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: 1. The materials stored with the exception of the activated carbon are noncombustible. There  are no other building or storage area contents
that constitute a fire hazard. Water from an automatic sprinkler system is not the  recommended fire suppression for any of these chemicals and several are reactive with  water.

2. This building is separate from other building and is not occupied
for any purpose other than monitoring, training or maintenance of equipment.

3. The carbon room building has a direct exit to the exterior and is separated from other  occupancies per table 508.4 (sprinklered occupancies) as shown on the attached plan.

4. A one hour rated corridor will be provided.
 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: The building is constructed of non-combustible construction and has no combustible  contents other than tanks and pumping equipment. Chemicals stored are hazardous  (oxidizers and corrosives) but not flammable or combustible.  The carbon has been  classified as a weakly explosive combustible dust and recommended practices are in place  to mitigate that hazard. The hardship is the cost of installing and maintaining an automatic  sprinkler protection in a room without a fire hazard, which in turn creates additional safety  hazards. In this case, the sprinkler system would not add any benefit to
safety
 
Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC 1015.1
Conditions: Two means of egress are required for each H-3 occupancy room based upon exceeding  the 25 feet common path of travel and the occupant load will exceed three during limited  periods of training and during a tank replacement and only a single side hinged swinging  door will be provided.

Conditions: Two means of egress are required for each H-3 occupancy room based upon exceeding  the 25 feet common path of travel and the occupant load will exceed three during limited  periods of training and during a tank replacement and only a single side hinged swinging  door will be provided.
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
2
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: The maximum travel distance will not exceed 75 feet.

The chemical storage rooms are normally unoccupied except for limited periods for  inspection testing and maintenance and normally that will occur with only one or two persons. Occasionally training or tank replacement may require more than three persons in the room.  

The materials in the room are oxidizers and corrosives but are not flammable or combustible.
 
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
 
  Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
  Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
Facts: The rooms are recessed for spill containment.  Adding an addition means of egress for the  limited hazard and occupancy would be difficult to accomplish without significantly increasing  the size of the building.