Project Information
Puerto Del Sol Restaurant
200 Main St
HOBART IN 46342
County LAKE
Project Type New   Addition   Alteration   Existing   Change of Occupancy Y
Project Status F F=Filed U or Null=Unfiled
IDHS Issued Correction order?    
Violation Issued by: NA
Local Building Official
Phone: 2199473407 Email: [email protected]
Local Fire Official 
2199473407 Email: [email protected]
Phone:

Variance Details
Code Name:  Other Code (Not in the list provided)
2014 IBC 675 12-6-3(a)
Conditions: Fire area exceeds 5,000 square feet
DEMONSTRATION THAT PUBLIC HEALTH, SAFETY, AND WELFARE ARE PROTECTED:
1=Non-compliance with the rule will not be adverse to the public health, safety or w
1
2= Applicant will undertake alternative actions in lieu of compliance with the rule to  ensure that granting of the variance will not be adverse to public health, safety, or  welfare.  Explain why alternative actions would be adequate (be specific).
Facts: Overall square footage is 70 sf over the 5,000 sf cut off for sprinklers if measured from exterior  wall to exterior wall. Exterior walls are 12" solid concrete. Actual interior usable space is 4,631 sf.
DEMONSTRATION OF UNDUE HARDSHIP OR HISTORICALLY SIGNIFICANT STRUCTURE:
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of physical limitations of the construction site or its utility services.
Y
Imposition of the rule would result in an undue hardship (unusual difficulty)  because of major operational problems in the use of the building or structure.
 
Y Imposition of the rule would result in an undue hardship (unusual difficulty)  because of excessive costs of additional or altered construction elements.
Imposition of the rule would prevent the preservation of an  architecturally or a historically significant part of the building or structure
 
Facts: It is unknown if the existing public water service is capable of supporting a fire sprinkler  system.  Building is not currently sprinkled and is constructed of solid concrete products.  Cost to install system would be extremely high due to a 70 sf overage of unusable space.