DHS

Indiana Department of Homeland Security / Fire and Building Safety Division

2019-20 version

 

Variance Application(s)



Steps:
1. First search for the type of variances to be displayed using search options.
2. Use Sort buttons to sort the variances.
3. For old variances, select Processed Applications along with dates.

Search for Applications

Fill these options below if you select **Processed applications option above in the list box above.
To get best response times narrow down search criteria recommended
Example search for a county or search for a 3 month time period with owner name like.,

Enter Variance Number
Enter Project Name like Example for Eli Lilly just enter lilly in the text box
** Enter Application From Date mm/dd/yyyy
** Enter Application To Date     mm/dd/yyyy
** Enter County Name
** Enter Code Type


Use Arrow buttons to sort the results by the column name.

Staff Recommendations Notations Explanation:
"A" category = staff recommendation is for approval with no equal alternatives because of noncompliance is not adverse. "B" category = staff recommendation is for approval with equal alternatives as stated by the proponent. "C" category = reserved, meaning staff believes Commission needs to discuss entirety. "D" category = recommendation is for denial. "I" category = incomplete (with permission of the Chairman). "NVR" category = no variance required. "T" category = tabled.
Variance Number/Id
Project Name
County
Variance Codes
18713 (Online)
Application Date:07/25/2018
Name Variance Information for ropes.pdf  Date:07/25/2018
The Rise at Chauncey  100 S. Chauncey Ave. 
West Lafayette 47906  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
TIPPECANOE 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
2.20.4, 2.20.4.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18713 8 mm ropes will be used in lieu of the required minimum diameter of 9.5mm.  
18722 (Online)
Application Date:08/07/2018
Name H-MRL Code Deviations.pdf  Date:08/07/2018
Heritage Woods of Noblesville  9600 E. 146th St. 
Noblesville   [ view application in html]
[ view app in pdf for IE ]
LFO acknowledgement received!
LBO Notified!
HAMILTON 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.26.8
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18722 (a) MRL Technology 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.1,3.19.4.4,3.19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) MRL Technology 
18724 (Online)
Application Date:08/09/2018
Name 03_AL-101-AL-101.pdf  Date:08/09/2018
Name 10_A-101-A-101.pdf  Date:08/09/2018
Name 24_AQ-101-AQ-101.pdf  Date:08/09/2018
Name Consultant Consent Form - signed.pdf  Date:08/09/2018
Caseys General Stores  116 National Rd W. 
RICHMOND 47374  [ view application in html]
[ view app in pdf for IE ]
Designer Affirmation Pending!
LFO Notified!
LBO Notified!
WAYNE 
Code Name:2010 Indiana Energy Conservation Code (675 IAC 19-4) [view code Details]
Specific Section:
5.4.3.4
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:18724 INCOMPLETE - CLARIFICATION, LBO,LFO,DESIGNER. 
18767 (Online)
Application Date:08/14/2018
Avant(Grand and Main)  12852 Old Meridian St 
Carmel 46032  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
HAMILTON 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC Section 1008.1.9
Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:Withdrawn by proponent 08/24/18. 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC Section 1008.1.9
Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:Withdrawn by proponent 08/24/18.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC Section 1004.1.2
Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:Withdrawn by proponent 08/24/18.  
Code Name:2014 IBC [view code Details]
Specific Section:
Section 1008.1.9
Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:Withdrawn by proponent 08/24/18.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IFC Sec. 3311.2
Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:Withdrawn by proponent 08/24/18.  
18801 (Online)
Application Date:08/29/2018
Name H-MRL Code Deviations.pdf  Date:08/29/2018
Hamilton Heights SC Project Vision PH 1 MS  25150 SR 19 
ARCADIA   [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO Notified!
HAMILTON 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.26.8
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18801 (a) MRL Technology. 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.1,3.19.4.4,3.19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) MRL Technology 
18809 (Online)
Application Date:09/05/2018
Name Cottage Mural Door.jpg  Date:09/05/2018
Auguste's Cottage Mural  762 N Dan Jones Rd 
Avon 46123  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
HENDRICKS 
Code Name:2008 Indiana Fire Code (675 IAC 22-2.4) [view code Details]
Specific Section:
Code 22-11-17-2
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:18809 INCOMPLETE - CODE EDITION, SECTION 
18813 (Online)
Application Date:09/08/2018
Name WHITE ROCK SUBMITTAL DWGS.pdf  Date:09/08/2018
White Rock Barn  6642 N State Rd 1 
OSSIAN 46777  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
WELLS 
Code Name:2014 IBC [view code Details]
Specific Section:
3401.1
Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:18813 WITHDRAWN BY PROPONENT. 
18859 (Online)
Application Date:09/19/2018
Name 12931_A101.pdf  Date:10/25/2018
Connersville Congregation of Jehovah's Witnesses Renovation  3171 East SR 44 
Connersville 47331  [ view application in html]
[ view app in pdf for IE ]
Designer Affirmation Pending!
LFO Notified!
LBO Notified!
FAYETTE 
Code Name:2014 Indiana Fire Code [view code Details]
Specific Section:
907.2.1
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:18859 The code requires a manual fire alarm system to be installed in Group A occupancy where the occupant load is 300 or more. The fire alarm system is to be monitored by an approved supervising station. The request is to have the monitored fire alarm system requirement omitted. Proponent states the maximum occupant load of the building is 180. What is the calculated occupant load?  
18861 (Online)
Application Date:09/28/2018
Name Petition Referral Form.pdf  Date:09/19/2018
Name 2314 Woodlawn - Permit Set (1).pdf  Date:09/28/2018
Name 2314 Woodlawn Class 2 Res Dev Permit Application Page 1.pdf  Date:09/28/2018
Name 2314 Woodlawn Class 2 Res Dev Permit Application Page 2.pdf  Date:09/28/2018
2314 Woodlawn Avenue  2314 Woodlawn Avenue 
Indianapolis 46203  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO Notified!
MARION 
Code Name: [view code Details]
Specific Section:
Bdroom window egress spec shee
Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:18861 WITHDRAWN BY PROPONENT 10/08/18. INCOMPLETE - CODE, EDITION, COMPLETION OF BOXES, CLARIFICATION 
18897 (Online)
Application Date:10/16/2018
Woodspring Suites Merriville  1500 E. 83rd Street 
Merriville 46410  [ view application in html]
[ view app in pdf for IE ]
LFO acknowledgement received!
LBO Notified!
LAKE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1-2007 Sec. 2.20.4
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:18897 Withdrawn by proponent 11/29/18. All variances. 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1-2007Sec. 2.18.4.2.5

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1-2007 Sec. 2.22.1.1

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1-2007 Sec. 2.18.5.1

18899 (Online)
Application Date:10/16/2018
Name Variance Application - State Project 400835 SET.pdf  Date:10/16/2018
IU Columbus Downtown Building Modifications  333 2nd St 
COLUMBUS 47201  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
Designer Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
BARTHOLOMEW 
Code Name:2008 Indiana Building Code (675 IAC 13-2.5) [view code Details]
Specific Section:
1008.1.9.3 Item 2
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:18899 INCOMPLETE - CODE EDITION, CLARIFICATION. 
18901 (Online)
Application Date:10/16/2018
TRK Medical Office Building  1425 Glendale Blvd. 
Valparaiso 46384  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
PORTER 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1, 2.22.1.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18901 (a) KONE is proposing to use polurethane buffers for this project until the 2016 becomes the standard for Indiana. 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
A17.1-2007, 2.20.4
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) Kone will utilize 8mm steel wire rope instead of the required minimum diameter of 9.5mm.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
A17.1-2007, 2.18.5.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(c) KONE EcoSpace Elevators will utilize 8mm governor rope instead of the required minimum diameter of 9.5mm.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
A17.1-2007, 2.18.4.2.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(d) The code requires speed-reducing switch to be of the manually reset type. The request is to allow the governor switch to be reset remotely from the controller. 
18984 (Online)
Application Date:11/29/2018
Name 646832-Layout.pdf  Date:11/29/2018
Holiday Inn Express  10040 Diebold Rd 
FORT WAYNE 46825  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO Notified!
ALLEN 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 yr 2.20.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18984 (a) Steel coated belts will be used as the suspension means.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 yr 2.18.5.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) Two Gen2 elevators will utilize 6.3 mm governor rope instead of the required minimum diameter of 9.5mm.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 yr 2.22.1.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(c) Two Gen2 elevators will use ACLA buffers in place of spring buffers.  
18991 (Online)
Application Date:12/03/2018
MDW Management LLC  300 Olive Street 
Wabash 46992  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO Notified!
LBO acknowledgement received!
WABASH 
Code Name:2011 NFPA 25 Inspection, Testing and Maintenance of Water Based Fire Protection Systems (675 IAC 28-1-12) [view code Details]
Specific Section:

Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:INCOMPLETE - SECTION, Hardship 
Code Name:2010 NFPA 13 Installation of Sprinkler Systems (675 IAC 28-1-5) [view code Details]
Specific Section:
675 IAC 28-1-5 Section 6.5.2
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:INCOMPLETE - Wrong section 
Code Name:2008 Indiana Building Code (675 IAC 13-2.5) [view code Details]
Specific Section:
Section 10 Chapter 9

19044 (Online)
Application Date:12/19/2018
Name H-MRL Code Deviations.pdf  Date:12/19/2018
Hendricks County Bank Offices  1 E. Main St. 
Brownsburg 46112  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
HENDRICKS 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.26.8
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19044 (a) MRL Technology 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.1,3.19.4.4,3.19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) MRL Technology 
19052 (Online)
Application Date:12/31/2018
Name EVSC - Construction Set V2.pdf  Date:12/31/2018
Name EVSC - Construction Set V2.pdf  Date:12/31/2018
Name North Elem School - Nature of non-compliance.pdf  Date:12/31/2018
Name North Elem School - Not adverse to HSW.pdf  Date:12/31/2018
Name North Elem School - Result in undue hardship.pdf  Date:12/31/2018
New Northside Elementary School  10701 Petersburg Road 
Evansville 47725  [ view application in html]
[ view app in pdf for IE ]
Designer Affirmation Pending!
LFO Notified!
LBO acknowledgement received!
VANDERBURGH 
Code Name: [view code Details]
Specific Section:

Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:VOID 
Code Name:1999 Indiana Electrical Code (675 IAC 17-1.5) [view code Details]
Specific Section:
300.10
Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:VOID 
Code Name: [view code Details]
Specific Section:

Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:VOID 
Code Name: [view code Details]
Specific Section:


Code Name:2009 Indiana Electrical Code (675 IAC 17-1.8) [view code Details]
Specific Section:
300.10
Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:VOID 
19072 (Online)
Application Date:01/14/2019
Name Variance Request.pdf  Date:01/14/2019
Name [4] REVISED CONSTRUCTION DRAWINGS C-01 [4]-Model.pdf  Date:01/14/2019
Retail Development  4305 East Michigan St 
INDIANAPOLIS 46201  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name:2014 IBC [view code Details]
Specific Section:
Section 1008.1.6 IBC
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:19072 The code requires landings at doors to have a width not less than the width of the stairway or the door, whichever is greater. The request is to allow the required landing to be omitted. Proponent states the building is more than 80 years old and there is only 1.7 feet between the building and the right-of-way which does not provide enough space to construct a 44 feet deep landing. When the building was originally constructed, the floor line was placed approximately 10-12 inches above the adjacent sidewalk and a small step was placed at each entry. The step has since deteriorated and is being replaced with a new step with a deeper tread and with handrails. 
19086 (Online)
Application Date:01/15/2019
Name 001AlarmBid.jpg  Date:01/15/2019
Name 002SprinklerBid.jpg  Date:01/15/2019
Name 003 BLDG Plan.jpg  Date:01/15/2019
Name 004 Purchase Price.jpg  Date:01/15/2019
Name 005 Improvement Price.jpg  Date:01/15/2019
Name 006TaxExeption.jpg  Date:01/15/2019
Name 007 2018 Code Inspection Report.jpg  Date:01/15/2019
Name 008 1 Code Occupancy R3 .jpg  Date:01/15/2019
Name 009 2 Code Occupancy R3.jpg  Date:01/15/2019
Name 010 1 State FMarshall Letter.jpg  Date:01/15/2019
Name 011 2 State FMarshall Letter.jpg  Date:01/15/2019
Name 012 3 State FMarshall Letter.jpg  Date:01/15/2019
Name GRACE Pictures.jpg  Date:01/15/2019
Name Building Inspection 1605_001.pdf  Date:01/15/2019
Name Division of Fire and Building Safety.pdf  Date:01/15/2019
Giving Recovery A Chance Everyday (GRACE)  6941 SR 64 
Marengo 47140  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
CRAWFORD 
Code Name:12-4-11 Change of Occupancy or Use of Existing Buildings [view code Details]
Specific Section:
12-4-11(b)
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:19086 WITHDRAWN BY PROPONENT 02/04/2019. 
Code Name:12-4-11 Change of Occupancy or Use of Existing Buildings [view code Details]
Specific Section:
12-4-11(b)
Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:VOID 
19089 (Online)
Application Date:01/15/2019
Name Cardinal Services_Floor Plan.pdf  Date:01/21/2019
Cardinal Services  500 S Buffalo St 
Warsaw 46580  [ view application in html]
[ view app in pdf for IE ]
Designer Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
KOSCIUSKO 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC Sec. 1015.1
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:19089 WITHDRAWN BY PROPONENT 02/27/19. The code requires adult daycare classrooms with a calculated occupant load exceeding 10 to have at least two exits out of each classrooms. The request is to allow the classrooms to have one exit. Proponent states the maximum occupant load in the classrooms will be limited to 10. Common path of travel from within the classrooms will be less than 50 feet; code permits 75 feet. Exit access travel distance will be less than 150 feet; code permits 200 feet. Building will be fully sprinklered as required. Grocery store is being converted into adult day services, offices, and warehouse for light manufacturing and skills training.  
19099
Application Date:01/18/2019
Name EVSC - Construction Set V2.pdf  Date:01/18/2019
Name August Order - SFM McCutchanville Re-inspection 8-30-18.pdf  Date:01/18/2019
Name North Elem School - Nature of non-compliance.pdf  Date:01/18/2019
Name North Elem School - Not adverse to HSW.pdf  Date:01/18/2019
Name North Elem School - Result in undue hardship.pdf  Date:01/18/2019
New Northside Elementary School  10701 Petersburg Road 
Evansville 47725  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
Designer Affirmation Pending!
LFO Notified!
LBO Notified!
VANDERBURGH 
19103 (Online)
Application Date:01/23/2019
Name H-MRL Code Deviations.pdf  Date:01/23/2019
Hancock Regional Health Phase 1 Clinic  200N and N 600W 
GREENFIELD 46104  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
HANCOCK 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3.26.8 ASME A17.1 2007
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19103 (a) MRL Technology. 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.1,3.19.4.4,3.19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) MRL Technology. 
19104 (Online)
Application Date:01/23/2019
Name H-MRL Code Deviations.pdf  Date:01/23/2019
Glasswater Creek Plainfield  10480 Glasswater Lane 
Plainfield 46168  [ view application in html]
[ view app in pdf for IE ]
Designer Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
HENDRICKS 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 3.26.8
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19104 (a) MRL Technology. 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.1,3.19.4.4,3.19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) MRL Technology. 
19105 (Online)
Application Date:01/23/2019
Name H-MRL Code Deviations.pdf  Date:01/23/2019
Jefferson High School Natatorium Renovations  1801 South 18th St 
LAFAYETTE 47905  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
TIPPECANOE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 3.26.8
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19105 (a) MRL Technology. 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.1,3.19.4.4,3.19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) MRL Technology. 
19106 (Online)
Application Date:01/23/2019
Name H-MRL Code Deviations.pdf  Date:01/23/2019
Ivy Tech Kokomo Campus Building 2  1901 E Morgan St 
KOKOMO 46903  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO Notified!
HOWARD 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 3.26.8
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19106 (a) MRL Technology. 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.1,3.19.4.4,3.19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) MRL Technology. 
19107 (Online)
Application Date:01/23/2019
Name H-MRL Code Deviations.pdf  Date:01/23/2019
Sala Motor Freight Line LLC  4940 & 4960 Decatur Blvd 
INDIANAPOLIS 00000  [ view application in html]
[ view app in pdf for IE ]
LFO acknowledgement received!
LBO Notified!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 3.36.8
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19107 (a) MRL Technology. 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.1,3.19.4.4,3.19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) MRL Technology. 
19109 (Online)
Application Date:01/24/2019
Name H-MRL Code Deviations.pdf  Date:01/24/2019
The Notch at Nora  8502 Westfield Blvd. 
Indianapolis 46240  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.26.8
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19109 (a) MRL Technology. 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.1,3.19.4.4,3,19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) MRL Technology. 
19112 (Online)
Application Date:01/25/2019
Name title page.PDF  Date:01/25/2019
Name S-1 Tippe Site.PDF  Date:01/25/2019
Name A-1.PDF  Date:01/25/2019
Name A-2.PDF  Date:01/25/2019
Name A-3.PDF  Date:01/25/2019
Name A-4.PDF  Date:01/25/2019
Name A-5.PDF  Date:01/25/2019
Name A-6.PDF  Date:01/25/2019
Name A-7.PDF  Date:01/25/2019
Name A-8.PDF  Date:01/25/2019
Name A-9.PDF  Date:01/25/2019
Name A-10.PDF  Date:01/25/2019
Name A-11.PDF  Date:01/25/2019
Name A-12.PDF  Date:01/25/2019
8 Unit Senior Patio Villas  101 102 Delmar Ct 
WARSAW 00000  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
KOSCIUSKO 
Code Name: [view code Details]
Specific Section:
2014 IBC 903.3.1.2 903.3.1.3
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:19112 The code requires at least an NFPA 13R sprinkler system to be provided in all buildings with a Group R fire area. The request is to allow an NFPA 13D system to be used in lieu of an NFPA 13R system. These are 1-story senior rental units. Units are separated with 1-hour wall as required, along with the garage.  
19138 (Online)
Application Date:02/12/2019
Green Acres Technology Park Office Building  10900 USA Parkway 
Fishers   [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
Designer Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
HAMILTON 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC, 712.1
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:19138 No plans 
19186 (Online)
Application Date:02/19/2019
Name Hampton Layouts.pdf  Date:02/19/2019
Name Hampton PD1.pdf  Date:02/19/2019
Name Hampton PD2.pdf  Date:02/19/2019
HAMPTON INN   361 Paris Dr 
FRANKLIN  46131  [ view application in html]
[ view app in pdf for IE ]
LFO acknowledgement received!
LBO Notified!
JOHNSON 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ANSI ASME A 17.1-2007, 2.20.1,
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19186 Schindler Elevator will utilize 6mm steel wire governor rope instead of the required minimum diameter of 9.5mm.  
19191 (Online)
Application Date:02/25/2019
The Mark at Fishers Disctrict  1242 Fishers Dr 
Fishers 46037  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO Notified!
HAMILTON 
Code Name:2012 Indiana Plumbing Cod, (675 IAC 16-1.4) [view code Details]
Specific Section:
305.8
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:19191 In concealed locations, piping installed through holes or notches in studs, joists, rafters, or similar members less than 1.5 inches from the nearest edge of the member is to be protected by shield plates having a minimum thickness of 0.062-inch-thick steel. The request is to allow nail guards 1"- " x 3" and 18GA thick to be used.  
19196 (Online)
Application Date:02/28/2019
Name Image (2).jpg  Date:02/27/2019
Name Image (2).jpg  Date:02/28/2019
Name Image-19 (1).jpg  Date:02/28/2019
Villas of Saxony  13233 E. 131st St. 
Fishers   [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
HAMILTON 
Code Name:2005 Indiana Residential Code (675 IAC 14-4.3) [view code Details]
Specific Section:
R311.5.6.2
Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:WITHDRAWN BY PROPONENT 03/04/19. 
19200 (Online)
Application Date:03/05/2019
Brooke Point Inn  4906 E 1200 N 
Syracuse 46567  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
KOSCIUSKO 
Code Name:2014 IBC [view code Details]
Specific Section:
903.2.8
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:19200 PLANS 
19282 (Online)
Application Date:03/20/2019
Holiday Inn Express  1548 Shook Dr. 
auburn 46706  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
DEKALB 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2.20.1,2.20.4,2.20.9 1 and 2 2
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19282 Schindler Elevator will utilize 6mm steel wire governor rope instead of the required minimum diameter of 9.5mm.  
19283 (Online)
Application Date:03/20/2019
Name H-MRL Code Deviations.pdf  Date:03/20/2019
Cummins Corporate Office Building Renovation  500 Jackson St 
COLUMBUS 47201  [ view application in html]
[ view app in pdf for IE ]
LFO acknowledgement received!
LBO Notified!
BARTHOLOMEW 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 3.26.8
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19283 (a) MRL Technology. 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3.19.4.1,3.19.4.4,3.19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) MRL Technology. 
19288 (Online)
Application Date:03/26/2019
Name 6284-1-Calculations IN-TLG 10-8-18.pdf  Date:03/26/2019
Name 6284-2-Calculations IN-TLG 10-8-18.pdf  Date:03/26/2019
Name TC183010 Brookside Park & Pool 6284-1 IN-TLG 10-8-18.pdf  Date:03/26/2019
Name U2010 Brookside Park & Pool 6284-2 IN-TLG 10-8-18.pdf  Date:03/26/2019
Brookside Park City of Indianapolis Parks  3500 Brookside Pkwy S. Dr 
INDIANAPOLIS 46201  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
675 IAC 13-2.5-17 Chapter 16
Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:VOID 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
Section 1608 2014 Indiana B.C.
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:19288 Snow load calculations will not be done on fabric canopy. Proponent states the canopy will be removed from the shade structure before winter and snow accumulation. This will be done as part of the shutdown and winterization of the park.  
19293 (Online)
Application Date:04/05/2019
Name H-MRL Code Deviations.pdf  Date:04/05/2019
Edgewood Primary School  7700 W. Reeves Rd. 
Bloomington   [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
Designer Affirmation Pending!
LFO Notified!
LBO Notified!
MONROE 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.26.8
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19293 (a)MRL Technology. 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.1,3.19.4.4,3.19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) MRL Technology. 
19294 (Online)
Application Date:04/05/2019
Name H-MRL Code Deviations.pdf  Date:04/05/2019
Renovations to Warsaw HS Cafeteria  1 Tiger Ln 
WARSAW 46581  [ view application in html]
[ view app in pdf for IE ]
LFO acknowledgement received!
LBO Notified!
KOSCIUSKO 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.26.8
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19294 (a) MRL Technology. 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.1,3.19.4.4,3.19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) MRL Technology. 
19295 (Online)
Application Date:04/05/2019
Name BELMONT ELEMENTARY -- FINALS.pdf  Date:03/27/2019
Name H-MRL Code Deviations.pdf  Date:04/05/2019
Belmont   1200 North Adams Drive 
DECATUR 46733  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
ADAMS 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.26.8
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19295 (a) MRL Technology. 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.1,3.19.4.4,3.19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) MRL Technology. 
19303 (Online)
Application Date:04/09/2019
Name 20190409_AMH 3rd Fl Admin - Pharmacy Renovation - A0-3 -Third Floor Life Safety Plan.pdf  Date:04/09/2019
Name 20190409_AMH 3rd Fl Admin - Pharmacy Renovation - A1-3 -Third Floor Demolition Plan.pdf  Date:04/09/2019
Name 20190409_AMH 3rd Fl Admin - Pharmacy Renovation - A2-3 -Third Floor Plan.pdf  Date:04/09/2019
Adams Memorial Hospital 3rd Floor Admin & Pharmacy Renovation  1100 Mercer Avenue 
Decatur 46733  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO Notified!
ADAMS 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC; Section: 1021.1
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:19303 WITHDRAWN BY PROPONENT 04/16/2019. The code requires two exit access stairways or ramps from the 3rd story. The request is to allow (3) elevator cabs in two locations to be used as temporary second exit from the 3rd floor. Portion of third floor is being renovated from In-patient Behavioral Health to administration and pharmacy. In buildings with four or more stories, elevator is permitted to be used as a means of egress, but must meet certain criteria. When is the construction date? 
19306
Application Date:04/11/2019
Name IMG_0981.JPG  Date:04/11/2019
Name IMG_0982.JPG  Date:04/11/2019
Name IMG_0983.JPG  Date:04/11/2019
Name IMG_0984.JPG  Date:04/11/2019
Name IMG_0985.JPG  Date:04/11/2019
Name IMG_0986.JPG  Date:04/11/2019
Name IMG_0987.JPG  Date:04/11/2019
Name IMG_0988.JPG  Date:04/11/2019
Name IMG_0989.JPG  Date:04/11/2019
Name IMG_0990.JPG  Date:04/11/2019
Name IMG_0991.JPG  Date:04/11/2019
Name IMG_0992.JPG  Date:04/11/2019
Name IMG_0993.JPG  Date:04/11/2019
Name c1.jpg  Date:04/11/2019
Name camp.jpg  Date:04/11/2019
Name 20x40_Fiesta_Schematic-1 Anchor.pdf  Date:04/11/2019
Name Overhead view 2 dig.pdf  Date:04/11/2019
Name Fire Resistance Cert.pdf  Date:04/11/2019
Name camptents.pdf  Date:04/11/2019
Summer Camp @ IUPUI  1001 W. New York St 
Indianapolis  46202  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO Notified!
LBO Notified!
MARION 
19310 (Online)
Application Date:04/12/2019
Name C400 Utility Plan.pdf  Date:04/12/2019
Oasis at 56th Street  4940 W 56th St 
Indianapolis 46254  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
NFPA 24, 1995, Section 3-3.2
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:19310 Withdrawn by proponent. 
19328 (Online)
Application Date:04/16/2019
Name Rope Certification.pdf  Date:04/16/2019
Name Final Drawings, Elev #1 and #2, 04-15-19.pdf  Date:04/16/2019
Name Final Drawings, Elev #1 and #2, 04-15-19.pdf  Date:04/16/2019
The Assembly/Ford Building  1301 E. Washington St. 
Indianapolis 46202  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
2007 IN Elev Code 2.20.4
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19328 (a) KONE EcoSpace Elevators with a capacity of 3,000-5,000# will utilize 8mm steel wire rope suspension cable instead of the required minimum diameter of 9.5mm. 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2007 IN Elev Code 2.18.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) KONE EcoSpace Elevators with a capacity of 3,000-5,000# will utilize 6mm steel wire governor rope instead of the required minimum diameter of 9.5mm. 
19359 (Online)
Application Date:04/18/2019
Name Variance Attachment 4-18-19.pdf  Date:04/18/2019
Name Variance Attachment 2 4-18-19.pdf  Date:04/18/2019
Post House  Vine Street and Northwest Third Street 
Evansville 47708  [ view application in html]
[ view app in pdf for IE ]
Designer Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
VANDERBURGH 
Code Name:2008 National Electrical Code [view code Details]
Specific Section:
2008 National Electrical Code
Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:19359 WITHDRAWN BY PROPONENT 04/23/2019. INCOMPLETE - COMPLETION OF BOXES,LBO, Article number.  
19373 (Online)
Application Date:04/23/2019
Name TAC32 H-MRL Code Deviations.pdf  Date:04/23/2019
St Paul Square  452 W Chicago St 
Valporaiso 46385  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
PORTER 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
33.19.4.1, 3.19.4.4, 3.19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19373 MRL Technology.  
19378 (Online)
Application Date:04/25/2019
Name H-MRL Code Deviations.pdf  Date:04/25/2019
1234 PROSPECT ST MIXED USE PROJECT  1234 PROSPECT ST 
INDIANAPOLIS 46203  [ view application in html]
[ view app in pdf for IE ]
Designer Affirmation Pending!
LFO Notified!
LBO acknowledgement received!
MARION 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
ASME A17.1 2007 3.26.8
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19378 (a) MRL Technology.  
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.1,3.19.4.4,3.19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) MRL Technology. 
19379 (Online)
Application Date:04/25/2019
Name H-MRL Code Deviations.pdf  Date:04/25/2019
Cook Central Plant  301 N. Curry Pike 
Bloomington 47404  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO Notified!
MONROE 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
ASME A17.1 2007 3.26.8
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19379 (a) MRL Technology.  
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.1,3.19.4.4,3.19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) MRL Technology.  
19381 (Online)
Application Date:04/25/2019
Name H-MRL Code Deviations.pdf  Date:04/25/2019
Union at Crescent  1100 N. Crescent Rd. 
Bloomington 47404  [ view application in html]
[ view app in pdf for IE ]
Designer Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
MONROE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 3.26.8
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19381 (a) MRL Technology.  
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.1,3.19.4.4,3.19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) MRL Technology.  
19382 (Online)
Application Date:04/25/2019
Name Belt TOC 1-28-15.docx  Date:04/25/2019
Name Belt LETTER 1.doc  Date:04/25/2019
Name EVO Belts.pdf  Date:04/25/2019
Name Belt Spec.pdf  Date:04/25/2019
Name Belt Design.pdf  Date:04/25/2019
Name Belt LETTER 1.doc  Date:04/25/2019
Name Shackle Counterside Installation.pdf  Date:04/25/2019
Name Shackle installation.pdf  Date:04/25/2019
Name Evolution 200 Inspector's Guide 44103.pdf  Date:04/25/2019
Name Shackle Drawing.pdf  Date:04/25/2019
Name Gates ft1 cert.pdf  Date:04/25/2019
Building 1 16 Tech  1218 Waterway Blvd. 
Indianapolis 46202  [ view application in html]
[ view app in pdf for IE ]
Designer Affirmation Pending!
LFO acknowledgement received!
LBO Notified!
MARION 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
2.14.1.7.1, 2.20.1, 2.20.2.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19382 (a) Requesting approval for an alternate method suspension of the Evolution MRL (EVO) series of elevator to the ASME A17.1 2007 code year.  
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
2.20.2.2,2.20.3,2.20.9,2.25.3
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) An approval for an alternate method suspension of the Evolution MRL (EVO) series of elevator to the ASME A17.1 2007 code year is being requested.  
19390 (Online)
Application Date:05/01/2019
Name IVYLAY.pdf  Date:05/01/2019
Name IVYPD.pdf  Date:05/01/2019
IVY TECH MUNCIE  205 W MAIN ST  
MUNCIE 47308  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO Notified!
DELAWARE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ANSI ASME A 17.1-2007, 2.20.1,
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19390 Schindler Elevator will utilize 6mm steel wire governor rope instead of the required minimum diameter of 9.5mm. 
19391 (Online)
Application Date:05/01/2019
Name M2083lay.pdf  Date:05/01/2019
Name M2083PD.pdf  Date:05/01/2019
Name M2082Lay.pdf  Date:05/01/2019
Name M2082PD.pdf  Date:05/01/2019
TARGET WEST LAFAYATTE  300 W STATE ST  
WEST LAFAYETTE 47906  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
TIPPECANOE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ANSI ASME A 17.1-2007, 2.20.1,
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19391 Schindler Elevator will utilize 6mm steel wire governor rope instead of the required minimum diameter of 9.5mm.  
19392 (Online)
Application Date:05/01/2019
Name WSLay.pdf  Date:05/01/2019
Name WSPD.pdf  Date:05/01/2019
WOODSPRING SUITES  1301 BASH STREET  
NDIANAPOLIS  46250  [ view application in html]
[ view app in pdf for IE ]
LFO acknowledgement received!
LBO Notified!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ANSI ASME A 17.1-2007, 2.20.1,
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19392 Schindler Elevator will utilize 6mm steel wire governor rope instead of the required minimum diameter of 9.5mm.  
19424 (Online)
Application Date:05/14/2019
Name 649924-Layout.pdf  Date:05/14/2019
Holiday Inn Express  300 Prosperity Dr 
WARSAW 46580  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO Notified!
LBO acknowledgement received!
KOSCIUSKO 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 yr 2.20.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19424 (a) Steel coated belts will be used as the suspension means.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 yr 2.18.5.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) Otis Gen2 Elevators will utilize 6.3 mm governor rope instead of the required minimum diameter of 9.5mm.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 yr 2.22.1.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(c) Two Gen2 elevators will use ACLA buffers in place of spring buffers.  
19460 (Online)
Application Date:05/16/2019
Name DINA-7.pdf  Date:05/22/2019
ILS  4508 Parnell ave 
Fort wayne 46825  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO Notified!
LBO Notified!
ALLEN 
Code Name:12-4-11 Change of Occupancy or Use of Existing Buildings [view code Details]
Specific Section:

Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:19460 WITHDRAWN BY PROPONENT 06/05/19. INCOMPLETE Completion of boxes, LFO e-mail address, specific code section. 
19464 (Online)
Application Date:05/21/2019
Name Bldg 9 Set.pdf  Date:05/21/2019
Name Bldg 10 Set.pdf  Date:05/21/2019
Name Bldg 11 Set.pdf  Date:05/21/2019
Name Bldg 12 16 Set.pdf  Date:05/21/2019
Name Bldg 13 Set.pdf  Date:05/21/2019
Name Bldg 14 Set.pdf  Date:05/21/2019
Name Bldg 15 Set.pdf  Date:05/21/2019
Centennial Highlands Phase 2  11828 Diebold Road 
Fort Wayne 46845  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
ALLEN 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC Section 903.3.1.2
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:19464 The code requires at least an NFPA 13R system to be installed throughout all buildings with a Group R fire area. The request is to allow an NFPA 13D system to be provided in lieu of the NFPA 13R system.  
19465 (Online)
Application Date:05/24/2019
Name LaQuinta Approved Set.pdf  Date:05/24/2019
LaQuinta Inn and Suites  3380 W Runkle Way 
BLOOMINGTON 00000  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
MONROE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
905.4
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:19465 INCOMPLETE - CODE, edition, hardship. 
19469 (Online)
Application Date:05/29/2019
Name Annotated A2 2 Sauder Feeds.pdf  Date:05/29/2019
Sauder Feeds  14033 Grabill Rd 
Grabill 46741  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
ALLEN 
Code Name:2014 IBC [view code Details]
Specific Section:
706.8
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:19469 The code limits any single opening in fire walls to a maximum of 156 sq. ft. The request is to allow the door opening in the fire wall to be 196 sq. ft. Proponent states having an opening that complies with code would result in damage being done to the fire wall system, vehicles, and safety.  
19472 (Online)
Application Date:06/04/2019
Building at 359 W Baker St  359 W Baker St 
Fort Wayne 46802  [ view application in html]
[ view app in pdf for IE ]
LFO acknowledgement received!
LBO Notified!
ALLEN 
Code Name:2014 IFC [view code Details]
Specific Section:
901.6.1
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:19472 The code requires fire protection systems to be inspected, tested and maintained in an operative condition at all times and is to be replaced or repaired where defective. The request is to allow the existing fire alarm system to remain unoperative.  
19479 (Online)
Application Date:06/06/2019
Miami Hills Apartments  3534 High Street 
South Bend 46614  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
ST JOSEPH 
Code Name:1985 Indiana Fire Prevention Code (675 IAC 22-2) [view code Details]
Specific Section:

Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:19479 Code edition, section, completion of box. 
19505 (Online)
Application Date:06/11/2019
Name Blackhawk Commons Variance.pdf  Date:06/11/2019
Blackhawk Commons Apartments  509 East 4th St 
SHERIDAN 46069  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
HAMILTON 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
Table 503 of IBC 2014
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:19505 The code prohibits buildings or structures from exceeding the height, number of stories, and allowable area based on the construction type. The request is to allow the R-2 occupancy to exceed the allowable area for the first floor by 6%. 
19506 (Online)
Application Date:06/11/2019
Name 657976-Layout.pdf  Date:06/11/2019
Sleep Inn Mainstay  7834 Progress Way 
Newberry 47449  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
GREENE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 yr 2.20.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19506 (a) Steel coated belts will be used as the suspension means.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 yr 2.18.5.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) One GEN2 elevator will utilize a 6.3 mm (1/4") diameter governor rope in lieu of the required minimum 9.5mm.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 yr 2.22.1.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(c) GEN2 Elevator will use ACLA buffers in place of spring buffers  
19509 (Online)
Application Date:06/11/2019
Name 657058-Layout.pdf  Date:06/11/2019
Name 657060-Layout.pdf  Date:06/11/2019
IU Health North Cancer Center Expansion  11700 N Meridian Street 
Carmel 46032  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO Notified!
LBO acknowledgement received!
HAMILTON 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 yr 2.20.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19509 (a) Steel coated belts will be used as the suspension means.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 yr 2.18.5.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) One GEN2 elevator will utilize a 6.3 mm (1/4") diameter governor rope in lieu of the required minimum 9.5mm.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 yr 2.22.1.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(c) GEN2 Elevator will use ACLA buffers in place of spring buffers.  
19517 (Online)
Application Date:06/11/2019
Name PHOTO1.pdf  Date:06/11/2019
Name PHOTO2.pdf  Date:06/11/2019
Name PHOTO3.pdf  Date:06/11/2019
Name PHOTO inside 1.pdf  Date:06/11/2019
Name Photo inside 2.pdf  Date:06/11/2019
Name GRACE SBC project _ 405429 2019-03-18 Existing Site Plan.pdf  Date:06/11/2019
Name GRACE SBC project _ 405429 2019-03-18 Exist Deck BLDG Access Plan.pdf  Date:06/11/2019
Name GRACE PROJECT ARCH DRWGS Project 01312019 .pdf  Date:06/11/2019
Name Fire Plan.pdf  Date:06/11/2019
Name GRACE Mobile Home Stamp Info.pdf  Date:06/11/2019
Name GRACE House History.pdf  Date:06/11/2019
Name Bill of sales.pdf  Date:06/11/2019
Name Bill of sales 2.pdf  Date:06/11/2019
Name Bill of sales 3.pdf  Date:06/11/2019
Name State of IN Inspection Letter.pdf  Date:06/11/2019
Name Fire Alarm System Quote.pdf  Date:06/11/2019
Name Inside photo 3.pdf  Date:06/11/2019
Name GRACE SBC project _ 405429 2019-03-18-Existing FND Plan.pdf  Date:06/11/2019
Giving Recovery A Chance Everyday  6941 E Sr 64 
MARENGO 47140  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO Notified!
LBO acknowledgement received!
CRAWFORD 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
IBS Rule 15 GAR Article 15.
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:19517 Withdrawn by proponent 06/29/19. Code requires an in plant inspection to be performed at the manufacturing facility by personnel from Building Commissioner's office. The request is to wave that requirement and have structure viewed as stick building complying with current code. 
19523 (Online)
Application Date:06/11/2019
Name VARIANCE FLOOR PLAN.pdf  Date:06/11/2019
Name VARIANCE APPROVAL LETTER 16-09-69.pdf  Date:06/11/2019
South Newton School Corporation   13232 South 50 East 
Kentland 47951  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
NEWTON 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC 1018.1
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:19523 Code requires corridors serving more than 30 occupants in Group E occupancy to be fire-resistance rated. The request is to allow the school to replace existing demountable corridor walls with non rated metal stud and gypsum board walls in same location. Smoke detectors tied to the building fire alarm system will be added in the corridors undergoing renovation and classrooms undergoing renovation. 
19526 (Online)
Application Date:06/11/2019
Name CJC Fire and Life Safety Plans .pdf  Date:06/11/2019
Consolidated Civil and Criminal Courthouse  2950 Prospect St 
Indianapolis 46203  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
Designer Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC 713.14.1
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:19526 Code requires an elevator lobby to be provided at each floor where an elevator shaft enclosure connects more than 3 stories .The request is to not have fire-rated elevator lobby vestibules in this 12 story high rise building. The building will be protected with an automatic sprinkler system per NFPA 13. 
19527 (Online)
Application Date:06/12/2019
University of Notre Dame New Women's Residence Hall  Holy Cross Drive and Wilson Drive 
Notre Dame 46556  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
ST JOSEPH 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
717.5.4.1 2014 IBC
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:19527 Code requires a listed smoke damper to be provided at each point a duct or air transfer opening penetrates a corridor enclosure. The request is to not install smoke dampers in supply ducts serving corridors. 2. The corridors will be provided with a smoke detection system connected to the building fire alarm system. 
19528 (Online)
Application Date:06/13/2019
Name WHITE ROCK SUBMITTAL DWGS_1.pdf  Date:06/13/2019
Name Chapter 34 Evaluation.pdf  Date:06/13/2019
Name 7448 - White Rock Barn Structure Analysis.pdf  Date:06/13/2019
White Rock Barn  6642 North State Road 1 
Ossian 46777  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
WELLS 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3401.3, 2901
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:19528 A) Code requires change of occupancy to comply for the required number of plumbing fixtures. The request is to allow portable restrooms to comply with fixture count. Permanent compliant restrooms will be provided within 2 years. Drinking water will be available during events. 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3401.1, 2014 IBC
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments: B) Code does not permit a chapter 34 to be used to convert structures other than class 1 structures to A and E occupancies. The request is for a barn to be converted to an A-2 occupancy Class 1 structure. Per the proponent, the building will pass the Chapter 34 evaluation for a change of occupancy to a Group A-2 Occupancy. A structural evaluation has been conducted. 
19529 (Online)
Application Date:06/14/2019
Name 1430 Meyer Road - OmniSource Eastside Retail - Fire Hydrant Distances (To Building).pdf  Date:06/14/2019
Name Fort Wayne Fire Department Inspection Report.pdf  Date:06/14/2019
Name Fort Wayne Fire Department Inspection Report.pdf  Date:06/19/2019
Private Fire Hydrant Decommission  1430 Meyer Road 
Fort Wayne 46803  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
ALLEN 
Code Name:2003 Indiana Fire Code (675 IAC 22-2.3) [view code Details]
Specific Section:
507.5.3
Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:VOID 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
IFC 2012 507.5.3;
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:19529 Code requires private fire service mains and water tanks to be periodically inspected,tested and maintained. The request is to place an out of service tag on the private hydrant and waive inspections, flow test and maintenance. Proponent states currently there is a city hydrant within 270 feet of OmniSource that would service facility extinguishing needs should they arise. 
19530 (Online)
Application Date:06/17/2019
Name concrete-filled steel columns.pdf  Date:06/17/2019
Name area plans - all floors.pdf  Date:06/17/2019
Name previous variance 09 09 35.pdf  Date:06/26/2019
Name Concrete-filled hollow steel column fire-resistance calculations (BRW Sealed).pdf  Date:07/02/2019
Allison Transmission Technical Innovation Center  10th and Cossell Road 
Speedway 46222  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: [view code Details]
Specific Section:

Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:VOID 
Code Name:2014 IBC [view code Details]
Specific Section:
722.1
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:19530 The code permits Chapter 5 of ASCE 29 to be used when calculating the fire resistance of steel assemblies. Proponent has elected to use this standard. The standard limits the unbraced length of steel to 13 feet. The request is to allow a new structure of Type I-B construction, having portions of its roof structure supported by concrete-filled steel columns, to have a length of approximately 27 feet. Per the proponent, the columns are located in large open spaces where the fire loading will be relatively low.  
19531 (Online)
Application Date:06/18/2019
Name Commerce Center Layout Drawings.pdf  Date:06/18/2019
Name Commerce Center Power Data.pdf  Date:06/18/2019
Commerce Center  400 E Lasalle 
South Bend 46617  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
ST JOSEPH 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
2.20.1,2.20.4,2.20.9 1 and 2 2
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19531 Schindler Elevator will utilize 6mm steel wire governor rope instead of the required diameter of 9.5mm. 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:

Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:VOID 
19532 (Online)
Application Date:06/18/2019
Name 201 S Main St Layout Drawings.pdf  Date:06/18/2019
Name 3 Rivers FCU Power Data.pdf  Date:06/18/2019
201 S Main St.  201 S Main St 
South Bend 46601  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
ST JOSEPH 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
2.20.1,2.20.4,2.20.9 1 and 2 2
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19532 Schindler Elevator will utilize 6mm steel wire governor rope instead of the required diameter of 9.5mm.  
19533 (Online)
Application Date:06/18/2019
Name Sleep Inn Fort Wayne Layout Drawings.pdf  Date:06/18/2019
Name Sleep Inn Fort Wayne Power Data.pdf  Date:06/18/2019
Sleep Inn Fort Wayne  5950 CROSS CREEK BLVD 
Fort Wayne 46809  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
ALLEN 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
2.20.1,2.20.4,2.20.9 1 and 2 2
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19533 Schindler Elevator will utilize 6mm steel wire governor rope instead of the required diameter of 9.5mm. 
19534 (Online)
Application Date:06/18/2019
Name 1 Cover - 21 W Canal.pdf  Date:06/18/2019
Name 2 Lower Level - 21 W Canal.pdf  Date:06/18/2019
Name 3 Canal St Level - 21 W Canal.pdf  Date:06/18/2019
Name 4 Upper Level - 21 W Canal.pdf  Date:06/18/2019
Name 5 Cross Sections.pdf  Date:06/18/2019
21 W Canal St Condo  21 W Canal St 
WABASH 46992  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
WABASH 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2012 IBC 903.2.8.1
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:19534 Code requires an automatic sprinkler system. The request is to avoid a sprinkler system. Applicant will install a fire alarm system within the apartment with heat and smoke detectors in the offices that occupy the floor below the living quarters of the residential unit. 
19536 (Online)
Application Date:06/22/2019
US Steel - Turbo Blower South  1 N. Broadway 
Gary 46402  [ view application in html]
[ view app in pdf for IE ]
LFO acknowledgement received!
LBO Notified!
LAKE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2017 2.27.3.2
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:19536 The code requires smoke and heat detectors to be provided in elevator hoistways. The request is to allow them to be omitted in the turbo blower south elevator. Proponent states having the detectors in the hoistway repeatedly trigger false alarms of the smoke and heat detectors due to building's heat, smoke, and dust. The elevator is not available or accessible to the general public. 
19537 (Online)
Application Date:06/24/2019
Name historical 3.pdf  Date:06/24/2019
Name historical 2.pdf  Date:06/24/2019
Name historical.pdf  Date:06/24/2019
Collective Beauty  136 E Main St 
Westfield 46074  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
HAMILTON 
Code Name:2014 IBC [view code Details]
Specific Section:
1109.2
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:19537 Code requires each toilet and bathing room to be accessible. The request is to omit this requirement. Proponent states they are only making small modifications to the building to create more business space for beauty salon type activities. Per the proponent, the building is part of the Westfield Historic District. Building is changing its use.  
Code Name:1989 Indiana Building Code (675 IAC 13-2.1) [view code Details]
Specific Section:
1109.2
Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:VOID 
19538 (Online)
Application Date:06/25/2019
Name Sliding Door Variance Floor Plan.docx  Date:06/25/2019
Horizontal Sliding Doors  319 N. Walnut St. 
Bloomington 47404  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
MONROE 
Code Name:1985 Indiana Fire Prevention Code (675 IAC 22-2) [view code Details]
Specific Section:
[B]1008.1.4.3
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:19538 Wrong code and edition, LFO's e-mail address. 
19539 (Online)
Application Date:06/25/2019
Name Fire Station MSKTD Drawing.docx  Date:06/25/2019
COLUMBIA CITY FIRE DEPARTMENT BABY BOX  112 S CHAUNCEY ST 
COLUMBIA CITY 46725  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
WHITLEY 
Code Name:2014 IFC [view code Details]
Specific Section:
(B) 1009.3.1.4.1
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:19539 The code prohibits openings other than those necessary for exit access stairway enclosures. The request is to allow a baby box to be installed in the stairway area. Proponent states the baby must be located in an easily accessible location for the firefighters.  
19540 (Online)
Application Date:06/27/2019
Name ComfortLayout.pdf  Date:06/27/2019
Name ComfortPD.pdf  Date:06/27/2019
COMFORT INN  522 ESSEX DR 
KOKOMO  46901  [ view application in html]
[ view app in pdf for IE ]
LFO acknowledgement received!
LBO Notified!
HOWARD 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ANSI ASME A 17.1-2007, 2.20.1,
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19540 Schindler Elevator will utilize 6mm steel wire governor rope instead of the required minimum diameter of 9.5mm. 
19541 (Online)
Application Date:06/27/2019
Name 4517 South Pointe Apartments_ProgressSet-Arch.pdf  Date:06/27/2019
South Pointe Apartments  Lantern Road & Fishers Pointe Blvd 
Fishers 46038  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
HAMILTON 
Code Name:2004 NFPA 82 Incinerators, Waste and Linen Handling Systems and Equipment (675 IAC 28-1-30) [view code Details]
Specific Section:
5.2.4.2, 5.2.5.3 and 5.2.7.1
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:19541 (a) NFPA 82 requires trash chute access rooms and termination rooms to be of 2-hour construction. The 2014 IBC permits 1-hour construction. The request is to allow the rooms to be of 1-hour construction. Similar variances have been granted in the past.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 InBC 1007.8
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) The code requires two-way communication at the elevator landing on each accessible floor that is one or more stories above or below the story of exit discharge. The request is to allow the new (4) story buildings, to not have the system. Most persons have cell phones. 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 InBC, 1209.2
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:(c) The code requires any attic area having a clear height of over 30" to have a 20" x 40" access opening. The request is to allow the opening to not be provided due to the roof truss diagonal bracing and planned insulation making access into the attic space very difficult. Proponent states there are only intermittent areas where the attic height is greater than 30 inches. 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2013 IN Swimming Pool, 20-2
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:(d) The code requires all Class A, Class B, and Class C Pools to be enclosed by a fence, wall, building, or other enclosures that is no lower than (6) feet high. The request is to allow a (4) foot high fence to be provided at the apartment patios at the first floor level.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 InMC, 918.6 Exc. 5.1
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:(e) Dwelling unit kitchen air will be returned to warm-air furnace. Return air intake will be approximately five (5) feet from the oven/range. Code requires ten (10) feet of separation and serve the kitchen only.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 InBC, 2902.1
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:(f) The code requires plumbing fixtures to be provided based on the occupancy and occupant load. The request is to allow the amenities area in Building 3 to only have (2) toilet fixtures or urinals per sex. Residents have access to their bathrooms in their apartment units. Two accessible restrooms will be provided.  
19542 (Online)
Application Date:06/28/2019
Name Vale View - Drawing Layouts Combined.pdf  Date:06/28/2019
Vale View  260 Franklin St 
VALPARAISO 46383  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO Notified!
PORTER 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 yr 2.22.1.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19542 (a) Two GEN2 Elevators will use ACLA buffers in place of spring buffers.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 yr 2.18.5.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) Two GEN2 elevators will utilize a 6.3 mm (1/4") diameter governor rope in lieu of the required minimum 9.5mm.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 yr 2.20.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(c) Three 43kN Steel Coated Belts and 646833 will utilize (4) 43kN belts as the suspension means. 
19543 (Online)
Application Date:07/01/2019
Name North Gibson PCPS Life Safety Plan.pdf  Date:07/01/2019
North Gibson Elemetary Hydronic Piping upgrade  813 N Archer St 
Princeton 47670  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
GIBSON 
Code Name:12-4-9 Maintenance of Existing Buildings and Structures [view code Details]
Specific Section:
12-4-9
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:19543 The code requires all buildings and structures to be maintained in conformance with the applicable rules of the Commission when constructed, installed, or altered. The request is to allow portions of the lay-in ceiling tile to not be in place during the use of the school building by the students. Proponent states the building is fully sprinklered with NFPA 13 system. Major piping renovations are being done during the next school year resulting in areas of ceiling being open during the school day.  
19544 (Online)
Application Date:07/01/2019
Name Huntington Police Dept - Final Elevator Drawings (6-25-19).pdf  Date:07/01/2019
Name H-MRL Code Deviations (002).pdf  Date:07/01/2019
City of Huntington New Police Station  450 Cherry St 
HUNTINGTON 46750  [ view application in html]
[ view app in pdf for IE ]
LFO acknowledgement received!
LBO Notified!
HUNTINGTON 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.26.8
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19544 (a) MRL Technology 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.1,3.19.4.4,3.19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) MRL Technology 
19545 (Online)
Application Date:07/02/2019
Name IHS Layout FINAL JPEG.jpg  Date:07/02/2019
Name IHS Layout Travel Path FINAL JPEG.jpg  Date:07/02/2019
Name IHS Evac Routes FINAL JPEG.jpg  Date:07/02/2019
Name Master-Flame-Spec-Sheet (2).pdf  Date:07/02/2019
Indy Horror Story, LLC  2002 Prospect St. 
Indianapolis 46203  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name:12-4-11 Change of Occupancy or Use of Existing Buildings [view code Details]
Specific Section:
675_IAC 12-4-11(b)
Staff Recommendation:T (explanation key at the top of the table)

Staff Comments:19545 The code prohibits the change of use of any building or structure unless the building or structure complies with the requirements for new construction or Chapter 34 Evaluation. The request is to allow an existing 6,000 sq. ft. retail building recently used as a church and now being converted into a special amusement building (similar to a haunted house) to not have to comply with the rules for new construction or Chapter 34 Evaluation. Building will not be sprinklered. Proponent states the building will be used from September - November, 36 nights and will be comprised of only 10 rooms totaling approximately 2,000 sq. ft. and 2-stories. Per the proponent, there will be a maximum of 24 guests in the entire building at a time in addition to 10 actors and 5 staff members. Eight guests at a time are escorted by staff from room to room. Smoke/fire detectors will be in each room with an alarm panel in a monitored control room. Each room will have a CCTV video camera. All staff, control room monitor and on-site police officer will stay in contact via 2-way radios. 
19547 (Online)
Application Date:07/03/2019
Stoll Brothers Lumber  509 S East St 
Odon 47562  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
DAVIESS 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:19547 (a) MRL Technology 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.4
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) MRL Technology 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(c) MRL Technology 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.26.8
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(d) MRL Technology 
19550 (Online)
Application Date:07/08/2019
Broadway Christian Church  910 
Fort Wayne 46802  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
ALLEN 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME 2.4.7.1
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:19550 Incomplete - code and edition 
19553 (Online)
Application Date:07/11/2019
Name 2018 IBC Excerpt - double top plate exception.pdf  Date:07/11/2019
Name Bath_exhaust_duct_photo.pdf  Date:07/11/2019
Name CityWay Bldg D floor plans.pdf  Date:07/11/2019
Name Flex duct spec sheet.pdf  Date:07/11/2019
Name CityWay TBR Violation.pdf  Date:07/11/2019
CityWay Phase 2 Building D  336 S Delaware St 
INDIANAPOLIS 46204  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
714.4.1.2, 2014 IBC
Staff Recommendation:T (explanation key at the top of the table)

Staff Comments:19553 A- (a) The code permits the ceiling membrane of 1- and 2-hour rated horizontal assemblies to be interrupted with the double wood top plate of a fire-resistance-rated wall assembly as long as all penetrating items through the double top plates are protected. The request is to allow the ceiling membrane of the 1-hour rated horizontal assemblies to be interrupted with the double wood top plate of a wall assembly that is sheathed with Type X gypsum wallboard in lieu of the wall being required to have a fire-resistance rating as permitted in the 2015 edition of the International Building Code. 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
714.4.1.3, 2014 IBC
Staff Recommendation:T (explanation key at the top of the table)

Staff Comments:(b) The code prohibits noncombustible penetrating items from connecting combustible materials past the point of firestopping unless it can be proved that the fire-resistance integrity of the horizontal assembly is maintained. The request is to allow bathroom exhaust ducts which penetrate the double top plate of the floor-ceiling and roof-ceiling assemblies to transfer from a hard duct to a flex duct after passing through the top plate. Proponent states the flex duct (combustible) and the hard duct (noncombustible) transfer well above the top plate penetration and therefore will not adversely impact the fire rating of the assembly. Building is fully sprinklered with NFPA 13R system as required.  
19554 (Online)
Application Date:07/11/2019
Name Klain Lot 1 7_11_19.pdf  Date:07/11/2019
Village Center Shoppes - Lot 1  2149 Glebe Street 
Carmel 46032  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO Notified!
LBO acknowledgement received!
HAMILTON 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC - 419.5
Staff Recommendation:T (explanation key at the top of the table)

Staff Comments:19554 The code requires live/work unit to be provided with a monitored fire alarm system and an automatic sprinkler system per NFPA 13R. The request is to not provide either, but provide a one hour fire-rated separation wall between the business area and the garage and a one hour fire-rated floor ceiling assembly between the business on the first floor and the residence units on the second floor. In addition, a 13-D fire sprinkler system will be installed in the R-Occupancy. Smoke/alarms will be wired between first and second floors. This is not identical to Variance #17-02-20. Variance has only 1 residential-unit on 2nd floor.  
19555 (Online)
Application Date:07/12/2019
Name Northrop High School Variance Plans.pdf  Date:07/12/2019
Northrop High School Renovation  7001 Coldwater Road 
Fort Wayne 46825  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
ALLEN 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
1009.8, 2014 IBC
Staff Recommendation:T (explanation key at the top of the table)

Staff Comments:19555 A- The code requires a floor or landing to be provided at the top and bottom of each stairway. The width of the landing cannot be less than the width of the stairway it serves, in this case 44 inches. Due to doors being installed at the bottom of the two stairs serving the auditorium balcony, the request is to allow the landings' width to be 37 inches. Proponent states the doors are being installed to block off access to the balcony from the first floor level when the balcony is not occupied for an event. The doors will be open during any event involving occupancy of the balcony. ***Sign stating, "Doors are to remain open during any event while balcony is occupied".  
19556 (Online)
Application Date:07/12/2019
Name Lancaster Lofts - 1st Floor, Loft Plan, Elevation.pdf  Date:07/12/2019
Name Lancaster Lofts_Development Plan_2019 06 21.pdf  Date:07/12/2019
Name 2018_IBC_Excerpt_-_Mezzanine_Exception.pdf  Date:07/12/2019
Lancaster Lofts  1633 East Market Street 
New Albany 47150  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
FLOYD 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
505.2.1, 2014 IBC
Staff Recommendation:T (explanation key at the top of the table)

Staff Comments:19556 The code limits the aggregate area of mezzanine or mezzanines within a room to no greater than 1/3 of the floor area of the room or space in which they are located. The request is to allow the loft mezzanines of the first floor dwelling units to be up to of the open area in the main floor of the unit per the 2018 IBC.  
19557 (Online)
Application Date:07/13/2019
Name KAR Overall First Floor Plan.pdf  Date:07/13/2019
Name Boon Edam Speed Lane Product Submittal_KAR.pdf  Date:07/13/2019
Name KAR.pdf  Date:07/17/2019
KAR Global Headquarters  11299 Illinois St. 
CARMEL 46032  [ view application in html]
[ view app in pdf for IE ]
LFO acknowledgement received!
LBO Notified!
HAMILTON 
Code Name:2014 IBC [view code Details]
Specific Section:
1008.3.1, IBC
Staff Recommendation:T (explanation key at the top of the table)

Staff Comments:19557 The code requires turnstiles more than 39 inches high to comply with the requirements for revolving doors. The request is to allow three 62 inches exterior exit turnstile to not comply with the requirements for revolving doors. Proponent states mainly it's the collapsibility issue. Revolving doors require that doors be able to collapse into a bookfold position with parallel egress paths providing an aggregate width of 36 inches. Does the turnstile comply with all the other revolving doors requirement? See e-mail.  
19558 (Online)
Application Date:07/13/2019
Name Bremen School Variance Exhibits.pdf  Date:07/13/2019
Name Bremen Elementary-MS - LFO Email.docx  Date:07/16/2019
Name Bremen Elementary-MS - LBO Email.docx  Date:07/16/2019
Bremen Elementary-Middle School Addition  700 West South Street 
Bremen 46506  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MARSHALL 
Code Name:12-4-12 Existing Buildings; Additions or Alterations [view code Details]
Specific Section:
Rule 4, Section 12(f), GAR

19559 (Online)
Application Date:07/13/2019
Name TAFF Building Variance Exhibits.pdf  Date:07/13/2019
Name Taff Building Sec 3412 Analysis.pdf  Date:07/13/2019
Taff Building Renovation  309 North Main Street 
Rushville 46173  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
RUSH 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
706.1.1, 2014 IBC

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
Table 3412.7, 2014

19560 (Online)
Application Date:07/15/2019
Name DOC071519-07152019091337.pdf  Date:07/15/2019
Name DOC071519-07152019091337.pdf  Date:07/15/2019
Name IDHS Written Comment Fillable Form.pdf  Date:07/16/2019
Manley Finish Grading Buiding 3  370 S Mitthoefer Rd 
INDIANAPOLIS 46229  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IFC, Sec. 507.5.1
Staff Recommendation:T (explanation key at the top of the table)

Staff Comments:19560 The code requires on-site fire hydrants and mains to be provided where a portion of a facility or building is more than 400 feet from a hydrant on a fire apparatus access road. The request is to allow Building 3, a 7,440 sq. ft. building used to store landscaping materials, straw mulch, and grass seed to be located more than 400 feet from a hydrant. Proponent states there is a detention pond on the property and an existing pond on the property to the south. However, fire official states no fire truck carries suction hoses. Building is located more than 30 feet from the property line and is 100 feet from the road. Per the proponent,the nearest fire hydrant is on Rawles Ave about 150 feet west of Mitthoefer Rd. If you measure a straight line from the hydrant to Building 3 it would be about 1,200 feet. The street route from Rawles to Mitthoefer to building 3 is about 1,850 feet. Proponent states there are no hazardous materials on the property. Per the fire official, variance #15-10-18 states no further construction is to be done. Fire official opposes variance. See attached letter.  
19561 (Online)
Application Date:07/15/2019
Name Black Dog Brewing_Life Safety Plans_Phase I.pdf  Date:07/15/2019
Name Black Dog_Chapter 34.pdf  Date:07/15/2019
Black Dog Brewing Company Phase 1  11230 N SR 67 
Mooresville 46158  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MORGAN 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC Sec. 3412.6.9
Staff Recommendation:T (explanation key at the top of the table)

Staff Comments:19561 A- The code requires a final score of zero or more in all categories, Fire Safety, Means of Egress, and General Safety in order to pass the Chapter 34 Evaluation. The request is to allow 5 points to be taken for a building having voice/alarm communication system with no fire command center in lieu of 0 points that is supposed to be taken when there is no command center. Proponent states the hardship is providing a 200 sq. ft. 1-hour rated fire command center. Fire command centers are typically required for high-rise buildings. 
19562 (Online)
Application Date:07/15/2019
Millwright Solutions LLC  300 Olive Street 
Wabash 46992  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
WABASH 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2012 IBC CH 9 SECTION 901.3

Code Name:2008 Indiana Building Code (675 IAC 13-2.5) [view code Details]
Specific Section:
-10 Chapter 9
Staff Recommendation:T (explanation key at the top of the table)

Staff Comments:19562 code and section 
19563 (Online)
Application Date:07/15/2019
Name Fire Submittal 20190715.pdf  Date:07/15/2019
Post Road Development  8641 Rawles Avenue 
Indianapolis  46239  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO Notified!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IFC Section D104.2
Staff Recommendation:T (explanation key at the top of the table)

Staff Comments:19563 wrong section 
19564 (Online)
Application Date:07/15/2019
Name BOOKED 1901 Crawfordsville Salt Building Drawings.pdf  Date:07/15/2019
Name BOOKED - 1901 - Crawfordsville Salt Specs.pdf  Date:07/15/2019
Name Legacy Drawings.pdf  Date:07/15/2019
Name Legacy Structural Analysis.pdf  Date:07/15/2019
Name Crawfordsville Salt Variance Application.pdf  Date:07/15/2019
Crawfordsville Salt PWP 5400 118 031D1  41 W 300 N 
CRAWFORDSVILLE 00000  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MONTGOMERY 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
903.2.11.1
Staff Recommendation:T (explanation key at the top of the table)

Staff Comments:no code ma 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
903.2.11.1
Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:VOID 
19565 (Online)
Application Date:07/15/2019
Name Taggart Memorial Venue Map and Rendering.pdf  Date:07/15/2019
Name Taggart Memorial Site Plan Exhibits.pdf  Date:07/15/2019
Name Riverside Park amphitheater could be a game-changer - Indianapolis Business Journal.pdf  Date:07/15/2019
Taggart Memorial Performance Venue  1856 Burdsal Pkwy 
INDIANAPOLIS 46208  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name:2010 Indiana Energy Conservation Code (675 IAC 19-4) [view code Details]
Specific Section:
4.1.1.1

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
503.1.1, 2014 IFC

19566 (Online)
Application Date:07/15/2019
Name BCC 3rd Floor PLan Renovation Project.pdf  Date:07/15/2019
Buckingham Office Renovation  941 N Meridian St 
INDIANAPOLIS 46204  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
716.5, 2014 IBC
Staff Recommendation:T (explanation key at the top of the table)

Staff Comments:19566 B- Code requires approved fire shutters in opening. The request is to remove the fire shutter and leave a 14' 8" opening. A row of sprinklers 6 feet on center, with a minimum of 18 gpm flow from each sprinkler will be installed to protect the opening. Proponent states the opening will be widened in order to provide space for employee lounge. 
19567 (Online)
Application Date:07/15/2019
Name 1234 Prospect - Exhaust Vent Variance Exhibit.pdf  Date:07/15/2019
Name 1234 Prospect St LifesafetyPlan.pdf  Date:07/15/2019
Name Copy of Exhaust Vent Pricing Options.xlsx  Date:07/15/2019
1234 PROSPECT ST MIXED USE PROJECT  1234 PROSPECT ST 
INDIANAPOLIS 46203  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
501.3.1, 2014 IMC

19568 (Online)
Application Date:07/16/2019
Name IUHB NICU Suite.pdf  Date:07/16/2019
IUH Bloomington Academic Health Center  SR46 and 14th Street 
Bloomington 47408  [ view application in html]
[ view app in pdf for IE ]
LFO acknowledgement received!
LBO Notified!
MONROE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 InBC Section 714.4.1.1.2

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 InBC Section 407.4.3.5.1

19569 (Online)
Application Date:07/16/2019
Name Citation Homes Office LFO Email.pdf  Date:07/16/2019
Name Citation Homes Google Earth.pdf  Date:07/16/2019
Name Citation Homes Google Earth Street View.pdf  Date:07/16/2019
NP 401  401 S. Earl Ave. 
Lafayette   [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
TIPPECANOE 
Code Name:12-4-12 Existing Buildings; Additions or Alterations [view code Details]
Specific Section:
675 IAC 12-4-12(b)(2)

19570 (Online)
Application Date:07/16/2019
Name VARIANCE Markeys Overall Site Plan with dimensions 7-1-19.pdf  Date:07/16/2019
Markey's Expansion  2365 Enterprise Park Pl 
INDIANAPOLIS 00000  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IFC 503.1.1

19571 (Online)
Application Date:07/16/2019
Name Hoosier Village Floor Plans.pdf  Date:07/16/2019
Hawthorn Hall Phase II  9915 Hoosier Village Dr 
ZIONSVILLE 46077  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
BOONE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC, 1018.6

19572 (Online)
Application Date:07/16/2019
Name 19-020 (KSM) Security Renovation_LIFE SAFETY 2019-07-10 Meeting Notes.pdf  Date:07/16/2019
Name 2019-020 KSM Security Reno_Variance Submission 2019-07-15.pdf  Date:07/16/2019
Katz Sapper & Miller Security Renovation  600 East 96th Street 
Indianapolis 46240  [ view application in html]
[ view app in pdf for IE ]
LFO acknowledgement received!
LBO Notified!
HAMILTON 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
1008.1.9, 2014 IBC

Code Name:12-4-11 Change of Occupancy or Use of Existing Buildings [view code Details]
Specific Section:
Rule 4, Section 9(a), GAR

19573 (Online)
Application Date:07/16/2019
hunted house  350 Anniston Dr 
Southport 46227  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO Notified!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3103.5
Staff Recommendation:T (explanation key at the top of the table)

Staff Comments:19573 no code or drawings, wrong LFO, LBO ma 
Code Name: [view code Details]
Specific Section:


19574 (Online)
Application Date:07/16/2019
Name Sweet Galilee of Anderson Drawings.pdf  Date:07/16/2019
Sweet Galilee at the Wigwam  Intersection of W. 14th St. and John St. 
Anderson   [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MADISON 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC, 1018.6

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC, 1018.1

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC, 714.4.1.2

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC, 3004.1

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC, 508.2.3

19575 (Online)
Application Date:07/16/2019
Name Riverfront Water Feature Plan and Details.pdf  Date:07/18/2019
Name Riverfront Water Feature Photos.pdf  Date:07/18/2019
Riverfront FW PhI Development Public Fountain  202 West Superior Street 
FORT WAYNE 46802  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
ALLEN 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
Rule 2, Section 3(b), ISPC

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
Rule 2, Section 27(a)

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
Rule 2, Section 3(e), ISPC

19576 (Online)
Application Date:07/16/2019
Name VARIANCE Allpoints Midwest 10 Drawings.pdf  Date:07/16/2019
AllpointsMidwest Building 10  1705 Midwest Drive 
Plainfield 00000  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
HENDRICKS 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2010 NFPA 72 26.6.3.2.1.4 (A)

19577 (Online)
Application Date:07/16/2019
Name Written Comment 115 Kirkwood.pdf  Date:07/19/2019
One15 Kirkwood - Condominiums & Retail  113/115 E. Kirkwood Avenue 
Bloomington   [ view application in html]
[ view app in pdf for IE ]
LFO acknowledgement received!
LBO Notified!
MONROE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC, 706.6.1

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC, Table 705.8

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC, 706.5, exc.1

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC, 706.1.1

19578 (Online)
Application Date:07/16/2019
Name Butler Sciences Variance Exhibit - sprinklered glass wall.pdf  Date:07/16/2019
Name Butler Sciences - 2nd Floor Pedestrian Walkway.pdf  Date:07/16/2019
Butler University Sciences Additions and Renovations  4600 Sunset Avenue 
Indianapolis 46208  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
707.6, 2014 IBC

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3104.5, 2014 IBC

19579 (Online)
Application Date:07/16/2019
Name 20190429 - BT Site Layout 24x36.pdf  Date:07/16/2019
Barnes & Thornburg Roof Terrace  11 South Meridian Street 
Indianapolis 46204  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
1009.1, 2014 IBC

19580 (Online)
Application Date:07/17/2019
Name KOKO Lay.pdf  Date:07/17/2019
Name KOKO PD.pdf  Date:07/17/2019
KOKOMO DOWNTOWN BUILDING  321 N MAIN ST 
KOKOMO 46901  [ view application in html]
[ view app in pdf for IE ]
LFO acknowledgement received!
LBO Notified!
HOWARD 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ANSI ASME A 17.1-2007, 2.20.1,

19581 (Online)
Application Date:07/17/2019
Name H-MRL Code Deviations.pdf  Date:07/17/2019
Alleyworks  217 West 6th Street 
Bloomington 47404  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
MONROE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3.26.8

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3.19.4.1,3.19.4.4,3.19.4.5

19582 (Online)
Application Date:07/17/2019
Name L8997Lay.pdf  Date:07/17/2019
Name L8997PD.pdf  Date:07/17/2019
Name L8879Lay.pdf  Date:07/17/2019
Name L8879Lay.pdf  Date:07/17/2019
Name L8879PD.pdf  Date:07/17/2019
Name L8879Lay.pdf  Date:07/17/2019
Name L8878PD.pdf  Date:07/17/2019
Name L8878Lay.pdf  Date:07/17/2019
Name L8878Lay.pdf  Date:07/17/2019
Name L8878Lay.pdf  Date:07/17/2019
WATERMARK AT FISHERS  9700 E 116TH ST 
FISHERS  46037  [ view application in html]
[ view app in pdf for IE ]
LFO acknowledgement received!
LBO Notified!
HAMILTON 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ANSI ASME A 17.1-2007, 2.20.1,

19583 (Online)
Application Date:07/17/2019
Name H-MRL Code Deviations.pdf  Date:07/17/2019
Valley House Flats Annex Bldg.  450 Main Street 
Brookville 47012  [ view application in html]
[ view app in pdf for IE ]
Designer Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
FRANKLIN 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3.19.4.1,3.19.4.4,3.19.4.5

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1 2007 3.26.8

19584 (Online)
Application Date:07/18/2019
Name Bluffton Harrison Overall Floor Plan.pdf  Date:07/18/2019
Bluffton Harrison Elementary School Add Renov  1100 East Spring Street 
Bluffton 46714  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
WELLS 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC, 1004.1.2, 1015.1

19585 (Online)
Application Date:07/19/2019
Name Wiley Floor Plans_Meeting Rooms.pdf  Date:07/19/2019
Wiley Indy Transformation  9200 Keystone Crossing 
INDIANAPOLIS 46240  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO Notified!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC Sec. 1008.1.2