Search for Applications

Fill these options below if you select **Processed applications option above in the list box above.
To get best response times narrow down search criteria recommended
Example search for a county or search for a 3 month time period with owner name like.,

Enter Variance Number
Enter Project Name like Example for Eli Lilly just enter lilly in the text box
** Enter Application From Date mm/dd/yyyy
** Enter Application To Date     mm/dd/yyyy
** Enter County Name
** Enter Code Type


Use Arrow buttons to sort the results by the column name.

Staff Recommendations Notations Explanation:
"A" category = staff recommendation is for approval with no equal alternatives because of noncompliance is not adverse. "B" category = staff recommendation is for approval with equal alternatives as stated by the proponent. "C" category = reserved, meaning staff believes Commission needs to discuss entirety. "D" category = recommendation is for denial. "I" category = incomplete (with permission of the Chairman). "NVR" category = no variance required. "T" category = tabled.
Variance Number/Id
Project Name
County
Variance Codes
17400
Application Date:01/30/2017
Name AE4931464 speedway indoor karting vio-signed.pdf  Date:02/17/2017
Speedway Indoor Karting  1067 Main Street 
Speedway 46224  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO Notified!
MARION 
Code Name:2014 IFC [view code Details]
Specific Section:
Sec. 1008.1.10(2014ED)
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:17400 TABLED BY COMMISSION 08/01/17. TABLED BY COMMISSION 07/06/17. TABLED BY COMMISSION 06/06/17. TABLED BY COMMISSION 05/04/17. TABLED BY COMMISSION 04/05/17. INCOMPLETE - LBO, Correct Section? Doesn't match description of variance. 
17488
Application Date:02/26/2017
Project Condor 5 AB Building  2059 S Tibbs Ave 
Indianapolis 46241  [ view application in html]
[ view app in pdf for IE ]
Designer Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name:12-4-9 Maintenance of Existing Buildings and Structures [view code Details]
Specific Section:
(d)
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:17488 WITHDRAWN BY PROPONENT 03/16/17. The code requires smoke and heat vents to be provided in F-1/S-1 occupancies having more than 50,000 sq. ft. in undivided area. The request is to allow the smoke and heat vents to be removed since the existing building will now be used as an F-2 occupancy and smoke and heat vents are not required for this occupancy. GAR allows removal of systems and features not required by current code. 
17513
Application Date:03/09/2017
River Ridge Tract 9B Building B  6200 Highway 62 
JEFFERSONVILLE 47130  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
CLARK 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2012 IBC/ 2014 Ind. Ammedments
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:17513 TABLED BY COMMISSION 04/05/17. INCOMPLETE - Code Section, LFO 
17585
Application Date:03/31/2017
Platform Deck For Deep River Adventure Park  9001 E Lincoln Hwy 
MERRILLVILLE 46307  [ view application in html]
[ view app in pdf for IE ]
LFO acknowledgement received!
LBO Notified!
LAKE 
Code Name:2010 Indiana Energy Code [view code Details]
Specific Section:
4.2.1.1
Staff Recommendation:NVR (explanation key at the top of the table)

Staff Comments:17585 (a) The code requires new buildings with conditioned space to comply with the 2010 Indiana Energy Code. The request is to allow the structures to have platform floors that will not comply with the Energy Code due to the platforms having no walls, roofs, lighting or heating. Floors will not be insulated.  
Code Name:2014 IBC [view code Details]
Specific Section:
1009, 1026 & 1027
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:(b) Exit stairs and ramps will not be provided. Instead, cargo nets, zip lines, bridges, rope bridges, and ladders will be provided. Platforms are less than 30 sq. ft. and is open on five sides and provides a climbing adventure for participants. 
17719
Application Date:05/26/2017
Harrison Springs Health Campus  871 Pacer Drive NW 
Corydon 47112  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO Notified!
LBO acknowledgement received!
HARRISON 
Code Name:Life Safety Code 101 2012 Edition [view code Details]
Specific Section:
Means of Egress 7.2.1.6.1.1
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:17719 Clarification  
17739
Application Date:06/06/2017
Party Barn  3352 West Union county line Rd 
Brownsville 47325  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO Notified!
UNION 
Code Name:2001 NFPA 15 Water Spray Fixed Systems (675 IAC 28-1-8) [view code Details]
Specific Section:

Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:17739 Clarification, owner, LBO 
17750
Application Date:06/09/2017
Cancer Treatment Center  701 Superior  
Munster 46321  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
LAKE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2.20
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:17750 INCOMPLETE -COMPLETION OF BOXES CODE and Edition. 
17789
Application Date:06/22/2017
11939 BUILDING  11939 N MERIDIAN ST 
Carmel 46032  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
HAMILTON 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2.20.1,2.20.4,2.20.9 1 and 2.1
Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:VOID 
17850 (Online)
Application Date:07/17/2017
Name 15014_SP0_Overall.pdf  Date:07/17/2017
Name 15014_SP2_underground pipe.pdf  Date:07/17/2017
Name 15014_SP3_Mechanical Room.pdf  Date:07/17/2017
Name 15014_SP4_SCHEM.pdf  Date:07/17/2017
Pulliam Square Phase 2  307 N Pennsylvania 
Indianapolis 46202  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
Designer Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name:Swimming Pool Code [view code Details]
Specific Section:
675 IAC 20-2-17
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:17850 The code requires pool circulation system to have a 2-hour turn over rate. The request is to allow the wading area/sun shelf to have a 2-hour turn over rate using its own separate circuit, and the rest of the pool to have a 6-hour turn over rate using its own separate circuit. 
17879 (Online)
Application Date:08/09/2017
Name A0.pdf  Date:08/09/2017
Name A1.pdf  Date:08/09/2017
Name previous variance.pdf  Date:08/09/2017
Carrier Warehouse Wall  7310 West Morris Street 
Indianapolis 46231  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO Notified!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
1016.2, Table 1016.2, 2014 IBC
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:17879 Withdrawn By Proponent 01/10/17. The code permits Group F-1 and S-1 occupancies to have a maximum travel distance of 250 feet in fully sprinklered buildings. The request is to allow the existing fully sprinklered manufacturing building to have a travel distance of 395 feet. A variance was granted in 2002 allowing the travel distance to be 395 feet. A new wall separating the manufacturing area from the storage area will be installed causing the existing egress paths to be rerouted. Proponent states the travel distance will stay the same (395 feet). 
17933 (Online)
Application Date:09/04/2017
Name Property Card.pdf  Date:09/04/2017
Name Variance Information.pdf  Date:09/04/2017
Name barn.jpg  Date:09/04/2017
Black Walnut Grove Estate  2860 E Contreras Pike 
West College Corn 47003  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
UNION 
Code Name:1990 Indiana Fire Prevention Code (675 IAC 22-2.1) [view code Details]
Specific Section:
903.2.1.2
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:17933 Waiting on Chapter 34. 
18003 (Online)
Application Date:10/02/2017
Name UND Family Layouts L1143.pdf  Date:10/02/2017
Name UND Family PD L1143.pdf  Date:10/02/2017
UND FAMILY HALL  Notre Dame Campus 
Notre Dame 46601  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
ST JOSEPH 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
2.20.1,2.20.4,2.20.9 1 and 2.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18003 Schindler Elevator will utilize 6mm steel wire governor rope instead of the required minimum diameter of 9.5mm.  
18006 (Online)
Application Date:10/02/2017
Name Sup Lofts G Layouts.pdf  Date:10/02/2017
Name Sup Lofts G PD.pdf  Date:10/02/2017
SUPERIOR LOFTS  102 W SUPERIOR ST 
FORT WAYNE 46802  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO Notified!
ALLEN 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
2.20.1,2.20.4,2.20.9 1 and 2.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18006 Schindler Elevator will utilize 6mm steel wire governor rope instead of the required minimum diameter of 9.5mm.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2
Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:VOID 
18009 (Online)
Application Date:10/03/2017
Name Woodspring Layouts.pdf  Date:10/03/2017
Name Woodspring PD.pdf  Date:10/03/2017
WOODSPRING SUITES - WHITESTOWN  6000 PERRY WORTH RD 
WHITESTOWN 46075  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
BOONE 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
2.20.1,2.20.4,2.20.9 1 and 2.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18009 Schindler Elevator will utilize 6mm steel wire governor rope instead of the required minimum diameter of 9.5mm.  
18011 (Online)
Application Date:10/03/2017
Name A-101 First Floor Plan Overall -.pdf  Date:10/11/2017
Name A-102 Second Floor Plan Overall -.pdf  Date:10/11/2017
Stonecrest At Meridian  8549 N Meridian St 
Indianapolis 46260  [ view application in html]
[ view app in pdf for IE ]
Designer Affirmation Pending!
LFO acknowledgement received!
LBO Notified!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
1007.8, 2014 IBC
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:18011 WITHDRAWN BY PROPONENT 10/20/17. The code requires two-way communication at the elevator landing on each accessible floor that is one or more stories above or below the story of exit discharge. The request is to allow the new (2) story and partial (1) story Assisted Living and Memory Care facility to not have the system. Instead, most persons have cell phones and will be used for communication. Similar variances have been granted in the past.  
18021 (Online)
Application Date:10/10/2017
Name Building Layout.pdf  Date:10/10/2017
Name Letter from Fire Official.pdf  Date:10/10/2017
Name Letter from Local Code Official.pdf  Date:10/10/2017
Name Notice of Violation.pdf  Date:10/10/2017
Name Photos.pdf  Date:10/10/2017
Name Site Plan.pdf  Date:10/10/2017
Name Variance Form.pdf  Date:10/10/2017
Overmeyer Heritage Barn Event Center  15034 SR 17 
Culver 46511  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO Notified!
MARSHALL 
Code Name:2014 Indiana Building Code [view code Details]
Specific Section:
903.2.1.3
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:18021 Chapter 34 
18038 (Online)
Application Date:10/17/2017
DEACONESS GATEWAY HOSPITAL  4011 GATEWAY BLVD. 
NEWBURGH 47630  [ view application in html]
[ view app in pdf for IE ]
Designer Affirmation Pending!
LFO Notified!
LBO Notified!
WARRICK 
Code Name: [view code Details]
Specific Section:
3.19.4.5
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:18038 INCOMPLETE - CODE, Edition, complete info in boxes. 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3.19.4.4
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:(b) INCOMPLETE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3.19.4.1
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:(c) INCOMPLETE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3.26.8

18064 (Online)
Application Date:10/18/2017
Name White Barn Venue_Plans.pdf  Date:10/23/2017
Name White Barn Venue_Photos.pdf  Date:10/23/2017
Name White Barn Venue_Chapter 34.pdf  Date:10/23/2017
Name Restroom Trailer Brochures.pdf  Date:10/23/2017
The White Barn Venue  501 Thomas Hill Road 
Madison 47250  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
JEFFERSON 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC Sec. 3401.1

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC Sec. 3401.3, 2902.1

18067 (Online)
Application Date:10/19/2017
Name G002-16195-EGRESS PLAN W COMBUSTIBLE AREA-FIRST FLOOR EGRESS PLAN.pdf  Date:10/19/2017
Name Green Cards Received 20171016.pdf  Date:10/19/2017
Name Signed Application.pdf  Date:10/19/2017
Puerto Del Sol Restaurant  200 Main St 
HOBART 46342  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
LAKE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC 675 12-6-3(a)
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:18067 INCOMPLETE - Code section 
18071 (Online)
Application Date:10/23/2017
Name 20160007-Architectural-Sheet - A8-1 - Stair Sections Plans-Layout1 (2).pdf  Date:10/23/2017
Name 4025 BONTERRA APARTMENTS BUILDING 3.pdf  Date:10/23/2017
Bonterra Apartments  13837 Coldwater Rd 
FORT WAYNE 00000  [ view application in html]
[ view app in pdf for IE ]
Designer Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
ALLEN 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
IBC 1009.3
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18071 The code permits exit access stairway to be open where the stairway serve or atmospherically communicate between only two stories. The request is to allow one exit access stairway to be atmospherically open from the first floor to the third floor. Draft curtains and closely spaced sprinklers in accordance with NFPA 13 will be located on the first and second floor. 
18079 (Online)
Application Date:11/01/2017
Name H-MRL Code Deviations.pdf  Date:11/01/2017
Annex 41  224 N Third St 
Terre Haute 47809  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
VIGO 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.1, 3.19.4.4, 3.19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18079 (a) MRL Technology. 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.26.8
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) MRL Technology. 
18123
Application Date:11/14/2017
Name 1A-IDHS Variance Application.pdf  Date:11/14/2017
Name 2A-B Coleman Hangar Plans.pdf  Date:11/14/2017
Name 3Aa-Photo-Typical Conduit Riser.pdf  Date:11/14/2017
Name 3Ab-Photo-Typical Conduit Riser Detail.pdf  Date:11/14/2017
Name 4A-Proposed Conduit Riser Detail.pdf  Date:11/14/2017
Name 5A-Conduit Seal Product Spec.pdf  Date:11/14/2017
Name 1B-IDHS Variance Application.pdf  Date:11/14/2017
Name 2B-B Coleman Hangar Plans.pdf  Date:11/14/2017
Name 3B-Electrical Gear Photo 1.pdf  Date:11/14/2017
Name 3B-Electrical Gear Photo 2.pdf  Date:11/14/2017
Name 4Ba-Electrical Room Location Plan.pdf  Date:11/14/2017
Name 4Bb-Electrical Room Detail.pdf  Date:11/14/2017
Name 4Bc-Electrical Room Detail View.pdf  Date:11/14/2017
New Hangar for B. Coleman Aviation  5701 West Industrial Highway 
Gary 46406  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
Designer Affirmation Pending!
LFO Notified!
LBO Notified!
LAKE 
18132 (Online)
Application Date:11/14/2017
Hamilton Heights High School Athletics & Vestibule Addition  25350 State Road 19 
Arcadia 46030  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
HAMILTON 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC Sec. 1018.1

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IFC Sec. 3311.2

18134 (Online)
Application Date:11/16/2017
Name VARIANCE Front of House.pdf  Date:11/16/2017
Name VARIANCE History Of Home.pdf  Date:11/16/2017
Name VARIANCE Monumental Stair.pdf  Date:11/16/2017
HAAN Mansion Museum of Indiana Art  920 E State Street 
Lafayette 47905  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
TIPPECANOE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC 903.2.1.3

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC 1008.1.2

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC 3401.1

18138 (Online)
Application Date:11/20/2017
Beach Tiki Bar & Grill  107 North Broadway 
Greensburg 47240  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
DECATUR 
Code Name:2008 Indiana Building Code [view code Details]
Specific Section:
903.2.1.2

18140 (Online)
Application Date:11/22/2017
Name 642802 Elevator Drawing (Revision 1).pdf  Date:11/22/2017
Butler University - Lacy School of Business  625 Butler Way 
Indianapolis 46208  [ view application in html]
[ view app in pdf for IE ]
Designer Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1-2007yr 2.18.4.2.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18140 (a) The Gen 2 at 200 system is designed to be compliant with A17.1 - 2007 with exception of components such as the alternate speed reducing switch technology which has A17.7 (AECO) approval. 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1-2007yr 2.18.5.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b)One Gen2 elevator will utilize 6.3 mm steel wire governor rope instead of the required minimum diameter of 9.5mm.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1-2007yr 2.22.1.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(c) One Gen2 elevator will use ACLA buffers in place of spring buffers.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1-2007yr 2.20.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(d) Steel Coated Belts will be used as the suspension means. 
18141 (Online)
Application Date:11/22/2017
Name Otis Layout Drawing Revised 6-2-2017.pdf  Date:11/22/2017
The Hub At West Lafayette  140 S Pierce St 
WEST LAFAYETTE 47906  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
Designer Affirmation Pending!
LFO Notified!
LBO acknowledgement received!
TIPPECANOE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1-2007yr 2.20.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18141 (a) Steel Coated Belts will be used as the suspension means. 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1-2007yr 2.18.4.2.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) The Gen 2 at 200 system is designed to be compliant with A17.1 - 2007 with exception of components such as the alternate speed reducing switch technology which has A17.7 (AECO) approval. 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1-2007yr 2.18.5.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(c) Three Gen2 elevators will utilize 6.3 mm steel wire governor rope instead of the required minimum diameter of 9.5mm.  
18151 (Online)
Application Date:12/05/2017
DEACONESS GATEWAY HOSPITAL  4011 GATEWAY BLVD 
NEWBURGH 47630  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO Notified!
WARRICK 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3.19.4.5
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:18151 INCOMPLETE -Code, Edition, completion of boxes. 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3.19.4.4

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3.19.4.1

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3.26.8

18153 (Online)
Application Date:12/05/2017
TECUMSEH HARRISON ELEMENTRY  2116 N 2ND ST. 
Vincennes 47591  [ view application in html]
[ view app in pdf for IE ]
Designer Affirmation Pending!
LFO acknowledgement received!
LBO Notified!
KNOX 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3.19.4.1
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:18153 INCOMPLETE -Code, Edition, completion of boxes.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3.26.8

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3.19.4.5

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3.19.4.4

18154 (Online)
Application Date:12/06/2017
Name The Hill Event Center 2-1-17.pdf  Date:12/06/2017
Hill Event Center LLC  525 S Church St 
FRENCH LICK 47432  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
ORANGE 
Code Name:2010 NFPA 13 Installation of Sprinkler Systems (675 IAC 28-1-5) [view code Details]
Specific Section:

Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:18154 INCOMPLETE - Code section, completion of boxes. 
18155 (Online)
Application Date:12/07/2017
Name 644502 - 503 Elevator Submittal Drawing.pdf  Date:12/07/2017
Marriott Courtyard  6315 Crawfordville Road 
SPEEDWAY 46224  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO Notified!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1-2007yr 2.20.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18155 (a) Steel Coated Belts will be used as the suspension means. 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1-2007yr 2.18.5.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) Two Gen2 elevator will utilize 6.3 mm steel wire governor rope instead of the required minimum diameter of 9.5mm.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1-2007yr 2.22.1.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(c) Two Gen2 elevator will use ACLA buffers in place of spring buffers. 
18156 (Online)
Application Date:12/07/2017
Name 639482-LAYOUT.pdf  Date:12/07/2017
Skyline Tower  855 Webster Street 
FORT WAYNE 46802  [ view application in html]
[ view app in pdf for IE ]
Designer Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
ALLEN 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1-2007yr 2.20.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18156 (a) Steel Coated Belts will be used as the suspension means.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1-2007yr 2.18.4.2.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) The Gen 2 at 200 system is designed to be compliant with A17.1 - 2007 with exception of components such as the alternate speed reducing switch technology which has A17.7 (AECO) approval. 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1-2007yr 2.18.5.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(c) Two Gen2 elevator will utilize 6.3 mm steel wire governor rope instead of the required minimum diameter of 9.5mm.  
18157 (Online)
Application Date:12/07/2017
Name TAC32 H-MRL Code Deviations.pdf  Date:12/07/2017
BROWNSBURG MIXED USE DEVELOPMENT  GREEN ST AT FRANKLIN ST 
BROWNSBURG 46112  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
HENDRICKS 
Code Name: ASME A17.1- 2007 [view code Details]
Specific Section:
3.26.8
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18157 (a) MRL Technology. 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.1, 3.19.4.7, 3.19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) MRL Technology. 
18161 (Online)
Application Date:12/11/2017
Name TAC32 H-MRL Code Deviations.pdf  Date:12/11/2017
Jackson County Judicial Center  220 E Walnut St. 
BROWNSTOWN 47220  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO Notified!
LBO Notified!
JACKSON 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.26.8
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18161 (a) MRL Technology. 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
3.19.4.1, 3.19.4.4, 3.19.4.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b) MRL Technology. 
18171
Application Date:12/12/2017
Name State Letter for J-Box access 11 30 2017.pdf  Date:12/12/2017
Tropicana Evansville Casino  421 Riverside Drive 
Evansville 47708  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
Designer Affirmation Pending!
LFO Notified!
LBO Notified!
VANDERBURGH 
18188 (Online)
Application Date:12/13/2017
Nichalos Pizza  530 N. Warpath Dr. 
Milan 47031  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
RIPLEY 
Code Name:12-4-11 Change of Occupancy or Use of Existing Buildings [view code Details]
Specific Section:
675 IAC 12-4-11(b)
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:18188 WITHDRAWN BY PROPONENT 12/20/17. The code prohibits a building from changing its character or use causing it to be classified within a different occupancy group, unless the building is made to comply with new construction or Chapter 34. The request is to allow an existing building previously used as a bingo hall (A-3 Occupancy) to be converted to a pizza shop (A-2 Occupancy)without being made to comply with either of the above. Proponent states the occupant load will not increase and the maximum travel distance to an exit is 75 feet, code permits 200 feet.  
18191 (Online)
Application Date:12/14/2017
Name VARIANCE A102 (Presentation).pdf  Date:12/14/2017
Name VARIANCE DEMO DRAWING A101.pdf  Date:12/14/2017
St. Michael Catholic Church  519 Jefferson Boulevard 
Greenfield 46140  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
HANCOCK 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC 903.2.1.3/707.3.10
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:18191 Code requires an automatic sprinkler system be provided for an A-3 occupancy if (one of the following are met) the fire area exceeds 12,000 sq. ft., the fire area has an occupant load greater than 300, and the fire area is located on a floor other than the level of exit discharge. The net increase of square feet to building is 3,038 square for a total area of 9,125 square feet. The fire area is under 12,000 square feet, but the existing occupant load of the building is 419 occupants and based upon new construction would require a fire suppression system or a 2-hour fire barrier separation between sanctuary and new circulation space. A Monitored fire alarm and smoke alarm system will be provided throughout existing and new floor areas. Proponent states occupant load will not be increased. Proponent does not want to add a sprinkler system or two hour fire barrier.  
18192 (Online)
Application Date:12/14/2017
Name VARIANCE Exchange A010 life safety (1).pdf  Date:12/14/2017
Name VARIANCE EXCHANGE ELEVATOR.pdf  Date:12/14/2017
Name Exchange A200 - ada.pdf  Date:01/18/2018
Name Exchange A201 - ada.pdf  Date:01/18/2018
Name 1VARIANCE HISTORIC LIST Exchange information for variance hearing.pdf  Date:01/18/2018
The Exchange  301 Massachusetts Avenue 
Indianapolis 46202  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC 1009.8

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ANSI A117.1 2009 404.2.1

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC 1013.3

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC 1012.2

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC 1009.7.2

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC 1009.4

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ANSI A117.1 2009 404.2.3.2

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC 1013.4

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ANSI A117.1 2009 405.2

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2009 ANSI A117.1 407.4.1 Fig b
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:(k) The code requires elevators with off-centered door to have inside dimensions of 68 inches wide and 54 inches deep. The request is to allow the existing elevator to have dimensions of 60 inches wide and 42 inches deep. Proponent states, the change of occupancy is what causing the elevator to be brought up to current code. Per the proponent, ADA would not have any jurisdiction based upon the scope of work and age of the building.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2009 ANSI A117.1 404
Staff Recommendation:VOID (explanation key at the top of the table)

Staff Comments:VOID 
18195 (Online)
Application Date:12/18/2017
Name 49-AQ101.pdf  Date:12/18/2017
Name 35-A101.pdf  Date:12/18/2017
Name 28-AL101.pdf  Date:12/18/2017
Name 2017_12-01 - State of IN Construction Design Release.pdf  Date:12/18/2017
Casey's Bremen, IN  1436 W Plymouth St. 
BREMEN 46506  [ view application in html]
[ view app in pdf for IE ]
LFO acknowledgement received!
LBO Notified!
MARSHALL 
Code Name:2010 Indiana Energy Code [view code Details]
Specific Section:
5.4.3.4, IECC 675IAC 9-4
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:18195 The code permits a vestibule to be omitted from a building entrance if the space served by the door is less than 3,000 sq. ft. The request is to allow the vestibule to be omitted. Proponent states the heating and air system comply with all codes for fresh air intake and exhaust. The building is balanced such that it is not pressurized. Similar variances have been granted in the past. One was granted last month.  
18196 (Online)
Application Date:12/20/2017
Name Storage Shed Plans Combined.pdf  Date:12/20/2017
Name 1815 S Kentucky.pdf  Date:12/20/2017
Name 1815 Kentucky Ave Plot Plan 010617.pdf  Date:12/20/2017
HIS Storage Shed  1815 Kentucky Ave. 
Indianapolis 46221  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 InFC 507.5.1
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:18196 Code requires all newly constructed buildings be within 400 feet of a hydrant. This proposed building will be nearly 800 feet from the nearest hydrant. The proponent is requesting not to install a hydrant. The building is constructed of lumber, laminated columns, and galvanized steel panels and will only be used to store concrete formwork and formwork hardware. There will be no combustible materials stored within or around the shed. The shed is "open-faced" with no doors. The surrounding area is covered in gravel with no vegetation. There are also no residential buildings within a quarter mile. The nearest building is operated by the proponent.  
18198 (Online)
Application Date:12/26/2017
Name State Letter Petition for J-Box access 12 12 2017.pdf  Date:12/26/2017
Tropicana Evansville Casino  421 NW Riverside Drive 
Evansville 47708  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
VANDERBURGH 
Code Name:2009 Indiana Electrical Code (675 IAC 17-1.8) [view code Details]
Specific Section:
314.29
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:18198 The code requires boxes, conduit bodies, and handhole enclosures to be installed so that the wiring contained in them can be made accessible without removing any part of the building. The request is to allow 200 junction boxes to be installed under floor panels which would cause the carpet to be cut in order to remove the access panels to get to the junction boxes. Proponent states it takes less than 5 minutes to make carpet cut, pull up an access panel and provide access to the junction boxes.  
18199 (Online)
Application Date:12/27/2017
Name IUHT Pharmacy - Mechanical.pdf  Date:12/27/2017
IU Health Tipton Hospital Pharmacy Renovation  1000 S. Main Street 
TIPTON 46072  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
TIPTON 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 InBC Section 717.6.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18199 Code requires ductwork that penetrates through a floor in an I-2 occupancy to be enclosed in a shaft. Proponent states that in four locations ductwork will penetrate through a floor level. A 90 minute fire damper assembly will be installed where ductwork penetrates a floor assembly. The building is fully sprinklered. This installation is a new installation routed through existing spaces. Due to the existing structure and utilities, the construction of a shaft enclosure will be difficult and also add the cost to construct shaft enclosures. Similar variances have been approved in the past. 
18201 (Online)
Application Date:01/02/2018
Fire Hose Removal  4301 Merchant Road 
Fort Wayne 46818  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
ALLEN 
Code Name:12-4-12 Existing Buildings; Additions or Alterations [view code Details]
Specific Section:
2014 Ind Fire Code 901.6.1
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:18201 The code allows non required fire protection equipment to either be tested and maintained or removed. The proponent is requesting the removal of the fire hose. Proponent states there are fire hydrants exterior to the building shared between other businesses in the area in the case of emergencies. Is the fire department in agreement with the removal of the hose? 
18202 (Online)
Application Date:01/03/2018
Hose Cabinets  2301 Fairfield Av.  
Fort Wayne  46807  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO Notified!
LBO acknowledgement received!
ALLEN 
Code Name:2014 InFire Code [view code Details]
Specific Section:
901.6.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18202 The code allows non required fire protection equipment to either be tested and maintained Or removed. The proponent is requesting the removal of 23 fire hoses. Proponent states fire department will not use the hoses. 
18203 (Online)
Application Date:01/03/2018
Name AH194 Lafayette_IN - Response to Fire Marshal - Variance.pdf  Date:01/03/2018
Name Lafayette IN - Response to Fire Marshal - Variance.pdf  Date:01/03/2018
Name Activity Report - PR-F18-F18-17-0060_A.pdf  Date:01/03/2018
Name C-1A.PDF  Date:01/08/2018
Name AH194_410_AS1-1_Site Plan 103017.pdf  Date:01/08/2018
Name As-Builts KMart - Cover (2).pdf  Date:01/18/2018
At Home #194 Lafayette, IN  3530 State Road 
Lafayette 74905  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
TIPPECANOE 
Code Name:2014 IBC [view code Details]
Specific Section:
Section 507.3
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:18203 The code permits Group B, E, F, M or S building no more than one story above grade plane to be unlimited in area where the building is fully sprinklered and is surrounded and adjoined by public ways or yards not less than 60 feet. This is a new tenant (M occupancy) moving into an existing tenant space (old Kmart - M occupancy). At the time the existing tenant space was constructed, the 60 feet surrounding the building was in place. Through the years, other tenant spaces started encroaching the 60 feet of required space. The request is to disregard the required 60 feet since the condition is existing and the new tenant is merely moving into the space (old Kmart) that was already there. Received e-mail from Lafayette Fire Official. He is not opposed to variance whether its an NVR or A category. Hes simply cleaning up an existing condition.  
18204 (Online)
Application Date:01/08/2018
Name 4356 Mill at Ironworks -CD Drawings.pdf  Date:01/08/2018
The Mill at Ironworks Plaza  209 W Front St 
MISHAWAKA 46544  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
ST JOSEPH 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 InBC, 713.4 713.7
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:18204 The code requires openings in shaft enclosure to be fire-resistance rated. The request is to allow a snow chute/shaft used for snow removal of the 5th tier of the parking garage to be open, with no protected opening, at the first floor.  
18205 (Online)
Application Date:01/08/2018
Name TAC32 H-MRL Code Deviations.pdf  Date:01/08/2018
Name HOLIDAY INN - HAMMOND -- final prints.pdf  Date:01/08/2018
Holiday Inn Express Hammond  2918 Carlson 
Hammond 46323  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
LAKE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3.19.4.1,3.19.4-5,3.26.8
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:18205 INCOMPLETE - Code, Edition, completion of box. 
18206 (Online)
Application Date:01/09/2018
Name PMMS Life Safety Plan.pdf  Date:01/09/2018
Perry Meridian Middle School and 5th Grade Academy Addition and Renovations  202 West Meridian School Road 
Indianapolis 46217  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
InBC 2014 1016.2, Tble 1016.2
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:18206 Code allows travel distance to be up to 250 ft. in a sprinklered building. Due to new additions to an existing middle school, the existing travel distance will become non-compliant. Currently the travel distance is approximately 249 ft. The request is, with the addition, to allow the travel distance to be approximately 273 ft. The entire school, new and existing, are protected with an automatic fire suppression system per NFPA 13. An existing smoke detection system will be maintained in the corridors, and will be extended into the corridors of the new construction and the entire system will be connected into the fire alarm system. Similar variances have been granted in the past. 
18207 (Online)
Application Date:01/09/2018
Name BBurg HS 2017 Unit G.pdf  Date:01/09/2018
Brownsburg HS 2017 Renovation and Addition  1000 S Odell Street 
BROWNSBURG 46112  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
HENDRICKS 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
InBC 2014 1023.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18207 The code requires the openings in one hour fire barriers to have one hour fire rated assemblies. The proponent is requesting a variance for a new one hour exit passageway to not require one hour fire rated assemblies. The entire building is protected by an automatic fire suppression system installed per NFPA 13. Close spaced sprinklers will be placed on the school side of the new glass doors and sidelights 6'-0" on center and no more than 12" away from the surface face per NFPA 13. Any glass will be either laminated or tempered. All other requirements of the exit passageways, including structural continuity, will be code compliant. Similar variances have been approved.  
18209 (Online)
Application Date:01/09/2018
Name AL-101.pdf  Date:01/09/2018
Name A-101.pdf  Date:01/09/2018
Name AQ-101.pdf  Date:01/09/2018
Casey's Gas City, IN  629 W. Main Street 
Gas City 46933  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO Notified!
GRANT 
Code Name:2008 Indiana Building Code (675 IAC 13-2.5) [view code Details]
Specific Section:
IBC 5.4.3.4, IECC 675IAC 9-4
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:18209 The code permits a vestibule to be omitted from a building entrance if the space served by the door is less than 3,000 sq. ft. The request is to allow the vestibule to be omitted. Proponent states the heating and air system comply with all codes for fresh air intake and exhaust. The building is balanced such that it is not pressurized. Similar variances have been granted in the past.  
18210 (Online)
Application Date:01/09/2018
Name Previous Variance 03-12-31.pdf  Date:01/09/2018
Name MS-C200_Overall Site Exhibit.pdf  Date:01/09/2018
Name MS_A101.pdf  Date:01/09/2018
Name Variance 03-12-31b.pdf  Date:01/18/2018
Name MS_AD201H.pdf  Date:01/18/2018
Name MS_A201H.pdf  Date:01/18/2018
Westfield Middle School Additions and Renovations  345 Hoover Street 
Westfield  46074  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
HAMILTON 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
InBC 2014 1003.2
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:18210A Code requires a ceiling height of 7'6" in egress pathways (corridor's). Proponent is requesting the remodel of an existing / remaining portion of a mechanical room / swimming pool spectator deck for use as a new corridor and locker room. The ceiling will be 7' in height. Proponent states that existing rooms and corridors under this area have been at the same ceiling height for more than a decade. The new additions as well as the existing school building are protected throughout by an automatic fire suppression system per NFPA 13.  
Code Name:12-4-12 Existing Buildings; Additions or Alterations [view code Details]
Specific Section:
12-4-12 (f)
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:(b) The code prohibits additions to building or structure plus the existing building from exceeding the allowable area based on the construction type. The request is to allow a new addition to be put to the existing building. Proponent states a variance was issued in 2003 that allowed an addition to be put to the existing building that was required to have at least 60 feet of open yard space surrounding it in order to be a building with unlimited area. At that time, 8.6% of the total building had less than 60 feet of frontage to a property line. The request is to allow a new addition to be put to the existing building placing the existing building in noncompliance. What is the sq. ft. of the existing building and new addition? Are there going to be any more additions constructed in the future putting the existing building in further noncompliance? 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
InBC Sec 1008.1.9
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:(c) The code requires free egress from the building - "readily openable from the egress side without the use of a key or special knowledge or effort". Proponent is requesting the use of a pressure control button to lock the "time-out" room. When the continuous pressure control button is released, the door is free to open. The building will be protected throughout with a NFPA 13 Sprinkler System. Two video cameras per room will be installed, one to monitor inside the room, the other looking at the door from the outside. Similar variances have been granted.  
18211 (Online)
Application Date:01/10/2018
Name Hoyt Ave House-FP-1.pdf  Date:01/10/2018
Hoyt  1301 Hoyt Ave. 
Indianapolis 46203  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name:2005 Indiana Residential Code (675 IAC 14-4.3) [view code Details]
Specific Section:
R302.2
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:18211 The Indiana Residential Code prohibits openings in the exterior wall of a dwelling or accessory building with a fire separation distance less than 3 feet measured perpendicular to the line used to determine the fire separation distance. The request is to allow a bedroom on the first floor to have two operable windows on the east property line. A sprinkler system has been designed and installed throughout the residence in accordance with NFPA 13D, 2010 edition.  
18212 (Online)
Application Date:01/10/2018
Cancer Treatment Center  701 Superior Avenue 
Munster  46321  [ view application in html]
[ view app in pdf for IE ]
LFO acknowledgement received!
LBO Notified!
LAKE 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
2.20.4
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18212 Elevator will use 6mm - 8mm ropes on elevator in lieu of the 9.5mm diameter.  
18215 (Online)
Application Date:01/13/2018
Name Autumn Trace Jennings County Life Safety Plan.pdf  Date:01/13/2018
Autumn Trace of Jennings County  Brookside Dr 
NORTH VERNON 47265  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
JENNINGS 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
1018.6, 2014 IBC
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:18215 The code states that rooms other than foyers, reception rooms, and lobbies are required to be separated from corridors and required to have rated assembles. The proponent is requesting that the activities area be allowed to open up into the rated egress corridor. The building is protected with a sprinkler system per NFPA 13R. The fire-rated corridor wall construction extends around the Activities area. Similar variances have been granted.  
18216 (Online)
Application Date:01/13/2018
Name Holiday Inn Express 1st Floor Plan.pdf  Date:01/13/2018
South Bend Holiday Inn Express  210 East Callander Street 
SOUTH BEND 46614  [ view application in html]
[ view app in pdf for IE ]
Designer Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
ST JOSEPH 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
1018.6, 2014 IBC
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:18216 Code requires rooms other than foyers, reception rooms, and lobbies to be separated from corridors where the corridor is required to have a fire rating. Proponent is building a hotel with the Breakfast Room and front Lobby being open to the 1st floor fire-rated egress corridor. The building will be protected with a sprinkler system per NFPA 13R. Other variances have been granted for similar requests.  
18217 (Online)
Application Date:01/13/2018
Name 130 E Washington Rooftop Concept.pdf  Date:01/13/2018
Name 130 East Washington ROOF DECK_12-19-2017_DRAFT.pdf  Date:01/13/2018
130 East Washington Street Rooftop Deck  130 East Washington Street 
Indianapolis 46204  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: ASME A18.1, 2005 2011 IESC [view code Details]
Specific Section:
2.7.1
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:18217 The Elevator/Lift Code limits the travel for platform lifts to a maximum of 14 feet. The request is to allow the wheelchair lift connecting the 12th floor of the building to the proposed rooftop deck to have a vertical travel of 16'6". Lift will be fully enclosed. Proponent states it will be costly to construct an elevator on the 12th floor of the existing building. Similar variances have been approved in the past where the travel exceeded 16'6". 
18218 (Online)
Application Date:01/13/2018
Name Variance Request 2.pdf  Date:01/13/2018
Renovations And Addition To Face Clinic  1505 Massachusetts Ave 
INDIANAPOLIS 46201  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
Designer Affirmation Pending!
LFO Notified!
LBO acknowledgement received!
MARION 
Code Name: [view code Details]
Specific Section:
1013.6
Staff Recommendation:I (explanation key at the top of the table)

Staff Comments:18218 INCOMPLETE - Code Edition, Completion of box. 
18219 (Online)
Application Date:01/15/2018
Name harley indy.pdf  Date:01/15/2018
Harley-Davidson of Indianapolis  12400 Reynolds Drive 
FISHERS 46038  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO Notified!
HAMILTON 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC 1008.1.2
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:18219 The code requires egress doors serving an occupant load of 50 or more to swing in the direction of travel. The proponents display area on the roof deck allows for more than 50 occupants, and has two points of egress. However, neither swing in the direction of travel. Proponent states the LFO has suggested to limit occupant load to no more than 50 persons. Sign will be posted within the multipurpose room restricting the roof deck area to a maximum occupant load of 50. The building if fully sprinklered. Deck is open to air. Per the proponent, changing door swing would cause infiltration problems during inclement weather.  
18220 (Online)
Application Date:01/15/2018
Name Classroom with Toilet Room.JPG  Date:01/15/2018
Blackhawk Christian School: South Campus Addi  7400 E. State Blvd 
FORT WAYNE 46815  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
ALLEN 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC 2902.2.2
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:18220 The code requires unisex toilet rooms to include only one water closet and only one lavatory. The request is to allow water closets to be provided in the classrooms for the Pre-K, K and 1st grade, but have the lavatories located within the classrooms outside the restrooms. This will be done in eight locations. Per the proponent, the restrooms are for classroom use only and not included in required fixture counts. Construction is completed.  
18221 (Online)
Application Date:01/16/2018
Name USI Arena Addition Progress Layouts.pdf  Date:01/16/2018
Name USI Arena Addition Progress Layouts.pdf  Date:01/16/2018
USI Arena and Kinesiology  8600 University Blvd 
EVANSVILLE 47712  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
Designer Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
VANDERBURGH 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1-2007yr 2.18.4.2.5
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18221 (a) The Gen 2 at 200 system is designed to be compliant with A17.1 - 2007 with exception of components such as the alternate speed reducing switch technology which has A17.7 (AECO) approval.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1-2007yr 2.18.5.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(b)One Gen2 elevator will utilize 6.3 mm steel wire governor rope instead of the required minimum diameter of 9.5mm.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1-2007yr 2.22.1.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(c) One Gen2 elevator will use ACLA buffers in place of spring buffers.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ASME A17.1-2007yr 2.20.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(d) Steel Coated Belts will be used as the suspension means. 
18222 (Online)
Application Date:01/16/2018
HOLIDAY INN EXPRESS PORTAGE  6295 MELTON RD 
PORTAGE 46368  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
PORTER 
Code Name:ASME A17.1 2007 [view code Details]
Specific Section:
2.18.5.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18222 Schindler Elevator will utilize 6mm steel wire governor rope instead of the required minimum diameter of 9.5mm. 
18223 (Online)
Application Date:01/16/2018
Name Ford Building Variance Drawings.pdf  Date:01/16/2018
Name Ford_Building_-_Images.pdf  Date:01/16/2018
Ford Building Renovation  1301 East Washington Street 
Indianapolis 46202  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
1007.2.1, 2014 IBC
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:18223 (a) The code requires at least one accessible elevator in buildings five (5) stories or more to be provided with standby power. The request is to not provide the standby power. Building is 4-stories Type I-B construction with an attached 1-story Type III-B construction building. Similar variances have been granted in the past.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
Table 601, 2014 IBC
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:(b) The code requires buildings of Type I-B construction to have 1-hour supporting structure and 1-hour rated roof assembly. The request is to allow two 1-story vestibules, 225 sq. ft. and 760 sq. ft. to be added to the existing Type I-B construction building, without having rated construction. The vestibules will be of noncombustible construction as required. Proponent states the aggregate area of the vestibules will increase the total building area by approximately 0.5%. The vestibules are designed as light-gauge structures with exposed steel. Building will be sprinklered throughout except for basement.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
706.6.1, 2014 IBC
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:(c) The code requires fire wall that separates buildings with different roof levels to terminate at least 30 inches above the lower roof level, with rated openings 15 feet above the lower roof. The request is to allow the 3-hour fire wall separating the Type I-B portion of the building from the III-B portion of the building to terminate just above the level of the lower roof surface. Basement level will not be sprinklered.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
3412.6.17, 2014 IBC
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:(d) The building is being evaluated per Sec. 3412.6.17 Chapter 34 Evaluation as a fully sprinklered building. The request is to allow the sprinkler system to be omitted on the basement level of the building and still be considered as a fully sprinklered building. Proponent states the basement will be unoccupied and will only be used to perform maintenance on piping. The doors to the basement will be locked with signage stating "Fire Department Personnel Only". No public or common access will be allowed in the basement. Basement is entirely of concrete construction.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
705.8, 2014 IBC
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(e) The code prohibits openings in exterior walls where the distance to the property line is less than 3 feet. The request is to allow new openings to be put into the east exterior wall in order to accommodate patios for first floor dwelling units. The distance to the property line will be 16. There is a 10 vacated alley. A sprinkler will be located at each opening on the 1st floor in the east exterior wall. The sprinklers will be positioned at the ceiling level within 12 inches of each opening. Similar variances have been granted in the past.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
712, 2014 IBC
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(f) The code requires opening(s) through a floor/ceiling assembly to be protected by shaft enclosure unless the opening(s) complies with one of the exceptions of the code. The request is to have a 5-story light well, located in the interior of the building, to provide natural light into the interior dwelling units on each floor, to not comply with any requirements for vertical openings, including rating as a 2-hour shaft enclosure, but be able to take credit on the Chapter 34 Evaluation as if there were 2-hour enclosures. The proponent advises sprinklers will be located at each window facing into the light well on each floor, positioned at the ceiling level within 12 inches of each window. Per the proponent, the hardship is that the light well is necessary to provide light into the interior of the building. Similar variance was granted in the past.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
716.5, 2014 IBC
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:(g) The code requires corridor walls to be fire-resistance protected with protected openings. The request is to allow the first floor corridor serving residential dwelling units to discharge through a front lobby with nonrated walls and openings. The walls affected will be protected by a row of sprinklers 6 feet on center on the room side.  
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
311.2.2, 2014 IFC
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:(h) The code requires sprinkler system to be maintained in an operable condition at all times. The request is to allow the existing sprinkler system in the building to be shut off as soon as combustible contents of the building have been removed. The system will be revised and made operational upon completion of the renovation. There is an exception that allows the shutdown of an existing system in vacant buildings when the premises have been cleared of all combustible materials and debris and, where approved by the code official, the type of construction, fire separation distance and security of the premises do not create a fire hazard. There is to be a tag posted at each fire department connection, system control valve, fire alarm control unit, fire alarm annunciator and fire command center stating that the sprinkler system has been placed out of service.  
18224 (Online)
Application Date:01/17/2018
Name SpringHill Camp Cabins Drawings.pdf  Date:01/22/2018
New Cabins for SpringHill Camps  2221 West State Road 258 
Seymour 47274  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
JACKSON 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC, 903.2.8
Staff Recommendation:C (explanation key at the top of the table)

Staff Comments:18224 Code requires all buildings with a Group R fire area to have a sprinkler system installed throughout the building. Proponent is building 8 new seasonal ranch cabins. The cabins are 840 sq. ft. with a maximum occupancy of 16 each and will be used seasonally, April through October. The maximum exit access travel distance for each cabin will be approximately 35 feet - code permits 200 feet. The cabins will not be used for cooking of any kind. The cabins will have no plumbing. The cabins will each have two (2) exits directly to the exterior with exit signs.  
18225 (Online)
Application Date:01/17/2018
Bohunsky Service Garage  3517 Rockville Road 
INDIANAPOLIS 46224  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO Notified!
LBO acknowledgement received!
MARION 
Code Name:2012 Indiana Plumbing Code. [view code Details]
Specific Section:
1003.4

18226 (Online)
Application Date:01/17/2018
Name ELSA Training Center Dorm Variance Drawings 1.pdf  Date:01/17/2018
ELSA Training Center  1240 Indiana 37 
EDGEWOOD 46036  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO Notified!
LBO Notified!
MADISON 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC, 1018.6
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:18226 The code requires corridors to be 1-hour fire-resistive construction and does not permit them to be interrupted by intervening rooms except for foyers, lobbies, and reception rooms. The variance request is to permit the lounge (1st floor), kitchenette/dining (1st floor), and kitchenette/dining (2nd floor) to be open to the corridor in the apartment building, R-2 Occupancy The building will be protected throughout with a sprinkler system per NFPA 13R. Smoke detectors tied to the fire alarm system will be provided in areas open to the corridor. The maximum travel distance to an exit is approximately 100 feet, code permits 200 feet. Similar variances have been granted. 
18227 (Online)
Application Date:01/17/2018
Name zehr dust collector drawing.pdf  Date:01/17/2018
ZEHR BUILDING - New Building  (Parcel 06-10-12-200-005)CR46A 
AUBURN 46706  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
DEKALB 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC 903.2.4.1
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18227 The code requires a sprinkler system to be provided throughout all Group F-1 occupancy fire areas that contain woodworking operations that exceeds 2,500 sq. ft. Proponent has a F-1 woodworking facility in a rural area with no city or public water supply. Proponent also states subdividing into 2500 sq. ft. areas with fire barriers is not practical for the manufacturing process. Fire area is 12,000 sq. ft. The facility will be provided with a dust collection system that will prevent the release of finely divided combustible waste or use of finely divided combustible materials. The dust collection system will be designed and installed per NFPA 664, 2012 Edition that includes exterior silo with collection manifold with individual connections to each cutting and sanding machine. The dust collection system will immediately evacuate the finely divided combustible waste from the building to exterior silo mitigating potential for risk of fire and/or explosion. Previous variances have been granted for similar requests. 
18228 (Online)
Application Date:01/17/2018
Name North Adams Variance Exhibits.pdf  Date:01/17/2018
Name IPS Lone Hall Variance Application - Utility Tunnel Sprinklers.pdf  Date:01/18/2018
NORTH ADAMS BP3 HS & MS INTERIOR RENOVATIONS  625 Stadium Drive 
DECATUR 46733  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
ADAMS 
Code Name:2010 NFPA 13 Installation of Sprinkler Systems (675 IAC 28-1-5) [view code Details]
Specific Section:
8.1.1
Staff Recommendation:A (explanation key at the top of the table)

Staff Comments:18228 The code requires sprinkler system to be installed throughout the premises in order to be allowed to have nonrated corridors. The request is to allow the sprinkler system to be omitted in the utility tunnels in the lower level of the school building, but be able to construct new corridors that will not be rated. Sprinkler system will be installed throughout the building additions and existing schools except for the utility tunnels. Proponent states tunnels are separated from the rest of the building with concrete construction. The tunnels are not occupied. 
18229 (Online)
Application Date:01/17/2018
Name 1634_OC1_Occupant_Plan_01-09-18.pdf  Date:01/17/2018
Salomon Farm Learning Center Addition  817 W Dupont Rd 
FORT WAYNE 00000  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
ALLEN 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
903.2.1.3 IBC (675 IAC 13-2.6)
Staff Recommendation:NVR (explanation key at the top of the table)

Staff Comments:18229 The code requires an automatic sprinkler system to be provided for Group A-3 occupancies with an occupant load greater than 300. Proponents occupant load calculations indicate an occupant load of less than 300 which does not require an automatic sprinkler system. The state plan reviewer calculated the occupant load to be over 300. The building is owned by the City of Fort Wayne and managed by the Fort Wayne Parks Department. Per the proponent, they have no desire to allow more than the calculated 285 occupants in the building and are willing to enforce that rule. *****BASED ON THE ATTACHED DRAWING, SPRINKLER SYSTEM IS NOT REQUIRED. PLANS SUBMITTED TO PLAN REVIEW DID NOT SHOW THE SEATING LAYOUT.  
18230 (Online)
Application Date:01/17/2018
Name Valparaiso High School Variance Exhibits.pdf  Date:01/17/2018
Valparaiso High School Natatorium Addition  2727 North Campbell Street 
Valparaiso 46385  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
PORTER 
Code Name:2010 NFPA 13 Installation of Sprinkler Systems (675 IAC 28-1-5) [view code Details]
Specific Section:
8.1.1

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
716.5, 2014 IBC

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
1016.1

18231 (Online)
Application Date:01/17/2018
Name Hendricks County Bank - New Corporate Offices - Brownsburg IN.pdf  Date:01/17/2018
Hendricks County Bank New Corporate Offices  East Main and Green Streets  
Brownsburg 46112  [ view application in html]
[ view app in pdf for IE ]
Designer Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
HENDRICKS 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
1018.1, 2014 IBC
Staff Recommendation:B (explanation key at the top of the table)

Staff Comments:18231 The code requires one hour rated corridors in a B occupancy when the occupant load is greater than 30. The request is to allow the egress corridors (walls and doors) constructed within the new corporate office building to not be fire-rated. The building will be provided with a manual fire alarm system and corridor smoke detection. They are not required by code. Maximum egress travel distance to an exit is 135 feet, code permits up to 200 feet. Three exterior exits will be provided. Similar variances have been granted in the past.  
18232 (Online)
Application Date:01/17/2018
Name 36 Franklin St Birds Nest Cafe Variance letter LBO.pdf  Date:01/22/2018
Name Birds Nest Cafe letter Health Dept.pdf  Date:01/22/2018
Name Exterior Photo.pdf  Date:01/22/2018
Name Birds Nest Cafe Drawings.pdf  Date:01/22/2018
Birds Nest Cafe  36 Franklin Street 
Nashville    [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
BROWN 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC, 1109.2

18233 (Online)
Application Date:01/17/2018
Name Cake Bake Shop Variance Exhibits.pdf  Date:01/17/2018
Cake Bake Shop  800 South Rangeline Road 
Carmel 46032  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
HAMILTON 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
706, 2014 IBC

18234 (Online)
Application Date:01/18/2018
Name Quality Woodcraft - Chapeter 34 Analysis.pdf  Date:01/18/2018
Name Quality Woodcraft - Sheet - S1 - Site Plan.pdf  Date:01/18/2018
Name Quality Woodcraft - Sheet - MEP1 - MEP.pdf  Date:01/18/2018
Name Quality Woodcraft - Sheet - C1 - Cover.pdf  Date:01/18/2018
Name Quality Woodcraft - Sheet - L1 - Life Safety.pdf  Date:01/18/2018
Name Quality Woodcraft - Sheet - A5 - Typical Sections.pdf  Date:01/18/2018
Name Quality Woodcraft - Sheet - A4 - Elevations.pdf  Date:01/18/2018
Name Quality Woodcraft - Sheet - A3 - Door & Window Schedules.pdf  Date:01/18/2018
Name Quality Woodcraft - Sheet - A2 - Mezzanine Plan.pdf  Date:01/18/2018
Name Quality Woodcraft - Sheet - A1 - Floor Plan.pdf  Date:01/18/2018
Quality Woodcraft  9921 N 1070 E 
Odon 47562  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
DAVIESS 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
Auto. Sprk. Sys. 903.2.4(4)

18235 (Online)
Application Date:01/18/2018
Name 4407 Trinitas ARCH.pdf  Date:01/18/2018
TRINITAS OFFICE RENOVATION  6344 CORNELL AVE 
INDIANAPOLIS 46220  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 InBC, 1109.2

18236 (Online)
Application Date:01/18/2018
Name Nativity Catholic Church Variance Exhibits.pdf  Date:01/18/2018
Nativity Catholic Church Addition and Renovation  7225 Southeastern Avenue  
Indianapolis 46239  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
Designer Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
507.5.1, 2014 IFC

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
903.2.1.3, 2014 IBC

18237 (Online)
Application Date:01/18/2018
Indiana Humanities Facility Upgrade  1500 North Delaware Street 
INDIANAPOLIS 46202  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ANSI A117.1 2009,Sec.804.5.5.3

18238 (Online)
Application Date:01/18/2018
Name IU Bicentennial Carillon Variance Exhibits.pdf  Date:01/18/2018
Indiana University Bicentennial Carillon  East 10th Street and North Fee Lane  
Bloomington 47408  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MONROE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
1009.10, 2014 IBC

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
1021.1, 2014 IBC

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
Table 503, 2014 IBC

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
1008.1.5, 2014 IBC

18239 (Online)
Application Date:01/18/2018
Name Morgan Building Drawings.pdf  Date:01/22/2018
Morgan Building  419 Main Street 
Lafayette   [ view application in html]
[ view app in pdf for IE ]
Designer Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
TIPPECANOE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC, 706.1.1

18240 (Online)
Application Date:01/18/2018
Name 4269 Annex 41 A201A-Paper.pdf  Date:01/18/2018
Name 4269 Annex 41 A201B-Paper.pdf  Date:01/18/2018
Name 4269 Annex 41 A202A-Paper.pdf  Date:01/18/2018
Name 4269 Annex 41 A202B-Paper.pdf  Date:01/18/2018
Name 4269 Annex 41 A251-Paper.pdf  Date:01/18/2018
Name 4269 Annex 41 A252-Paper.pdf  Date:01/18/2018
Name 4269 Annex 41 A253-Paper.pdf  Date:01/18/2018
Name 4269 Annex 41 A254-Paper.pdf  Date:01/18/2018
Name 4269 Annex 41 A255-Paper.pdf  Date:01/18/2018
Annex 41  224 N Third St 
Terre Haute 47809  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
VIGO 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 InBC, 1109.2

18241 (Online)
Application Date:01/18/2018
Name A2-1 - DEMO AND FLOOR PLAN.pdf  Date:01/18/2018
Name A3-4 - INTERIOR ELEVATIONS.pdf  Date:01/18/2018
Name A3-4 - INTERIOR ELEVATIONS.pdf  Date:01/18/2018
Name 5611 Progress Road VIO18-000355 01-17-2018 SAS NOV.pdf  Date:01/18/2018
Precision Rings  5611 Progress Road 
INDIANAPOLIS 46241  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ANSI A117.1 2009: 308.3.2

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
IBC 2014: 1109.13

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
ANSI A117.1 2009: 902.4

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
IBC 2014: 1109.3

18242 (Online)
Application Date:01/18/2018
Name Riley Park Pool Drawings.pdf  Date:01/22/2018
Name Riley Park Pool Site Plans.pdf  Date:01/22/2018
Riley Park Pool Renovation  300 Apple Street 
Greenfield   [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
HANCOCK 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
675 IAC 20-2-27

18243 (Online)
Application Date:01/18/2018
Name 2018-01-18-171230 WOB Indy Rev 03.pdf  Date:01/18/2018
World of Beer Bar + Kitchen  409 Massachusetts Ave 
INDIANAPOLIS 46204  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 InBC, Section 1009

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2009 ANSI A117.1 - 404.2.4

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 InBC, 1003.2

18244 (Online)
Application Date:01/18/2018
Name NHMS_VariancePlan.pdf  Date:01/18/2018
North Harrison MS-Physical Education Addition  1180 Highway 64 NW 
Ramsey 47166  [ view application in html]
[ view app in pdf for IE ]
LFO Notified!
LBO Notified!
HARRISON 
Code Name:2010 NFPA 13 Installation of Sprinkler Systems (675 IAC 28-1-5) [view code Details]
Specific Section:
8.2.1

18245 (Online)
Application Date:01/18/2018
Name Tab Stadium_Rooftop and Floor Plans.pdf  Date:01/19/2018
Stadium Facility for Tabernacle Presbyterian  418 E 34th St 
INDIANAPOLIS 46205  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC Sec. 1109.12.3

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC Sec. 1013

18246 (Online)
Application Date:01/18/2018
Name Harrison Barn_Life Safety Floor Plan.pdf  Date:01/19/2018
Reception Hall for Harrison Wedding Barn  5465 S State Road 75 
Jamestown 46147  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO Notified!
LBO Notified!
BOONE 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC Sec. 903.2.1.2

18247 (Online)
Application Date:01/18/2018
Name Adams Central Sprinkler and Nonrated Corridor Drawing.pdf  Date:01/22/2018
Name Adams Central Temporary Dead End Varinace Drawing.pdf  Date:01/22/2018
Name Adams Central Drawings.pdf  Date:01/22/2018
Name Adams Central Phasing Plan.pdf  Date:01/22/2018
Adams Central Community Schools  222 W. Washington Street 
Monroe 46772  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
Designer Affirmation Pending!
LFO Notified!
LBO acknowledgement received!
ADAMS 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IFC, 3311.2

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC, 706

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC, 1018.1

18248 (Online)
Application Date:01/18/2018
Clyde Theatre Renovation  1808 Bluffton Rd 
FORT WAYNE 46809  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
ALLEN 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IFC, 901.6

18249 (Online)
Application Date:01/18/2018
Name MALTRIN 305 Wet Process Narrative.docx  Date:01/18/2018
Name 305_WET_BLDG_AREA_EXHIBITS.pdf  Date:01/18/2018
Name GPC - 1997 Code Variance Documentation.pdf  Date:01/18/2018
Grain Processing Corporation Maltrin Expansion  1443 South 300 West 
Washington 47501  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
Designer Affirmation Pending!
LFO Notified!
LBO acknowledgement received!
DAVIESS 
Code Name:12-4-12 Existing Buildings; Additions or Alterations [view code Details]
Specific Section:
Rule 4, Section 12(f), GAR

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
712.1, 2014 IBC

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
903.2.4, 2014 IBC

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
905.3.1, 2014 IBC

18250 (Online)
Application Date:01/18/2018
Name MALTRIN Packaging Tower 307-306 Process Narrative.docx  Date:01/18/2018
Name 306-307_PKG_TWR_SPRAY_DRYER_AREA_EXHIBITS.pdf  Date:01/18/2018
Name GPC - 1997 Code Variance Documentation.pdf  Date:01/18/2018
Grain Processing Corporation 306-307 Maltrin Exp  1443 South 300 West 
Washington 47501  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
Designer Affirmation Pending!
LFO Notified!
LBO acknowledgement received!
DAVIESS 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
1021.1, 2014 IBC

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
903.2.4, 2014 IBC

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
503.1, 2014 IBC

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
712.1, 2014 IBC

Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
403, 2014 IBC

18251 (Online)
Application Date:01/18/2018
Name PFW Music Technology Center New and Existing Floor Plans.pdf  Date:01/18/2018
Purdue Fort Wayne Music Technology Center  4835 Kroemer Road 
Fort Wayne 46818  [ view application in html]
[ view app in pdf for IE ]
Designer Affirmation Pending!
LFO Notified!
LBO Notified!
ALLEN 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
1018.1, 2014 IBC

18252 (Online)
Application Date:01/18/2018
Sandwich Shop Cosmopolitan on the Canal  310 W. Michigan St 
Indianapolais 46202  [ view application in html]
[ view app in pdf for IE ]
Ready for IDHS processing!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IMC 506.4.2

18253 (Online)
Application Date:01/19/2018
Name Regenstrief Headquarters Floorplans.pdf  Date:01/19/2018
Name A-403 and A404 - Stair plans.pdf  Date:01/19/2018
Name Plumbing - Roof Drain.pdf  Date:01/19/2018
Name Email Correspondence with City 2014.pdf  Date:01/19/2018
Regenstrief Institute Inc - Headquarters  1111 W 10th Street 
Indianapolis 46204  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO acknowledgement received!
LBO acknowledgement received!
MARION 
Code Name:2003 ANSI A117.1 [view code Details]
Specific Section:
604.5.1

Code Name:2003 ANSI A117.1 [view code Details]
Specific Section:
404.2.3

Code Name:2008 Indiana Building Code (675 IAC 13-2.5) [view code Details]
Specific Section:
1011.3

Code Name:2008 Indiana Building Code (675 IAC 13-2.5) [view code Details]
Specific Section:
1020.1.2

18254 (Online)
Application Date:01/19/2018
Name A1 1 Annotated Flr Plan.pdf  Date:01/19/2018
Name LS1 1 Life Safety Plan.pdf  Date:01/19/2018
Zore's Towing - Building 7  1300 N. Mickley Ave 
INDIANAPOLIS 46224  [ view application in html]
[ view app in pdf for IE ]
Owner Affirmation Pending!
LFO Notified!
LBO acknowledgement received!
MARION 
Code Name: Other Code (Not in the list provided) [view code Details]
Specific Section:
2014 IBC 1104.4 Exc # 1