DHS

Indiana Department of Homeland Security / Fire and Building Safety Division

2020-21 version

 
AE Permit(s)[1]   BPV[0]   Elevator(s)[1]   Child Care(s)[0]   Fireworks Retail[0]   Fireworks Wholesale[0]   Health Care(s)[0]   Other(s)[0]   School(s)[0]   Plan(s)[0]   UST(s)[0]   Complaint Inspection(s)[0]  

Down Load Facility Files:
Rode Floor Plan.pdf,Upload Date:06/20/2019

Rodeheaver Floor Plan 2018.pdf,Upload Date:08/17/2018

Rode Stage 2018.pdf,Upload Date:08/17/2018

Rodeheaver - 23May2017.pdf,Upload Date:12/06/2017

AE43662-05022016.pdf,Upload Date:05/02/2016

AE43662-02252016.pdf,Upload Date:02/25/2016

Rodeheaver.pdf,Upload Date:12/16/2015

All Campus Buildings.pdf,Upload Date:12/16/2015

Rode.pdf,Upload Date:11/19/2014

OCC map.pdf,Upload Date:02/13/2014

AE43662.jpg,Upload Date:02/13/2014

AE43662 2012 Rodeheaver Auditorium 901 Park Ave Winona.pdf,Upload Date:04/05/2013

AE-43662-01292013.jpg,Upload Date:02/18/2013

Inspections for: AE43662

[Upload file /photos]
Inspection Details
COMPLIED Facility Id:AE43662 Facility Name:RODEHEAVER AUDITORIUM/ GYM
Inspection Date: 07/29/2019 Inspection Status: COMPLIED ;Inspection Type: Annual
Inspector: MICHAEL GEARHART ;Record Created Date:07/29/2019
Sprinkler: G  Alarm: G  Remarks:Did inspection with Scott 
Facility matched [view inspection report] [update / view this inspection] [add reinspection]
NOTES Facility Id:AE43662 Facility Name:RODEHEAVER AUDITORIUM/ GYM
Inspection Date: 08/20/2018 Inspection Status: NOTES ;Inspection Type: Annual
Inspector: ED SORENSEN ;Record Created Date:08/20/2018
Sprinkler:   Alarm:   Remarks:AE PERMIT NOTICE IN E-MAIL. APPROVED AND SENT TO SCOTT AITES. 
[view inspection report] [update / view this inspection] [add reinspection]
COMPLIED Facility Id:AE43662 Facility Name:RODEHEAVER AUDITORIUM/ GYM
Inspection Date: 08/13/2018 Inspection Status: COMPLIED ;Inspection Type: Annual
Inspector: ED SORENSEN ;Record Created Date:08/13/2018
Sprinkler:   Alarm: G  Remarks:INSPECTED WITH SCOTT AITES. SOME EXIT DOORS WERE STICKING AND NEEDED ADJUSTMENT AND WERE ADJUSTED TO MAKE THEM OPEN MORE EASILY. COMPLIED FOR 2018. PER MIT STILL NEEDS TO BE RENEWED IN NOVEMBER. 
Facility matched [view inspection report] [update / view this inspection] [add reinspection]
COMPLIED Facility Id:AE43662 Facility Name:RODEHEAVER AUDITORIUM/ GYM
Inspection Date: 02/05/2018 Inspection Status: COMPLIED ;Inspection Type: Reinspection
Inspector: ED SORENSEN ;Record Created Date:02/05/2018
Sprinkler:   Alarm: G  Remarks:FIRE ALARM PAPERWORK E-MAILED TO ME. I REVIEWED IT -FOUND NO ISSUES. COMPLIED FACILITY AND E-MAILED PERMIT. 
[view inspection report] [update / view this inspection] [add reinspection]
Facility Id:AE43662 Facility Name:RODEHEAVER AUDITORIUM/ GYM
Inspection Date: 01/25/2018 Inspection Status: VIOLATION ;Inspection Type: Reinspection
Inspector: ED SORENSEN ;Record Created Date:01/25/2018
Remarks:REINSPE TED WITH SCOTT AITES. 
Facility matched [view inspection report] [update / view this inspection] [add reinspection] [violation order]
Facility Id:AE43662 Facility Name:RODEHEAVER AUDITORIUM/ GYM
Inspection Date: 11/21/2017 Inspection Status: VIOLATION ;Inspection Type: Annual
Inspector: ED SORENSEN ;Record Created Date:11/21/2017
Remarks:INSPECTED WITH SCOTT AITES OF GRACE COLLEGE WHO OWNS BUILDING. 
Facility matched [view inspection report] [update / view this inspection] [add reinspection] [violation order]
COMPLIED Facility Id:AE43662 Facility Name:RODEHEAVER AUDITORIUM/ GYM
Inspection Date: 12/12/2016 Inspection Status: COMPLIED ;Inspection Type: Reinspection
Inspector: ED SORENSEN ;Record Created Date:12/12/2016
Sprinkler:   Alarm: G  Remarks: 
[view inspection report] [update / view this inspection] [add reinspection]
Facility Id:AE43662 Facility Name:RODEHEAVER AUDITORIUM/ GYM
Inspection Date: 09/09/2016 Inspection Status: VIOLATION ;Inspection Type: Annual
Inspector: ED SORENSEN ;Record Created Date:09/09/2016
Remarks:RENOVATIONS COMPLETED. INSPECTED BUILDING WITH BRITTON. 
Facility matched [view inspection report] [update / view this inspection] [add reinspection] [violation order]
NOTES Facility Id:AE43662 Facility Name:RODEHEAVER AUDITORIUM/ GYM
Inspection Date: 08/22/2016 Inspection Status: NOTES ;Inspection Type: Site Visit
Inspector: ED SORENSEN ;Record Created Date:08/22/2016
Sprinkler:   Alarm:   Remarks:INSPECTED WITH JONI. THEY STILL NEED TO REPLACE EXTERIOR DOORS.(THEY HAVE REQUESTED THE WORK) I WILL NEED TO GO BACK IN TWO WEEKS TO VERIFY DOOR REPLACEMENT AS THEY WERE STICKING WORSE THAN BEFORE WHEN I WAS HERE. I WILL BE WRITING A NEW VIOLATION REPORT UNLESS DOORS WORK PROPERLY. 
Facility matched [view inspection report] [update / view this inspection] [add reinspection]
NOTES Facility Id:AE43662 Facility Name:RODEHEAVER AUDITORIUM/ GYM
Inspection Date: 06/14/2016 Inspection Status: NOTES ;Inspection Type: Site Visit
Inspector: ED SORENSEN ;Record Created Date:06/14/2016
Sprinkler:   Alarm:   Remarks:SITE VISIT. SPOKE WITH MANAGER JONI. THEY HAVE NOT COMPLETED RENOVATIONS YET. SHE WILL CALL ME IN A FEW WEEKS TO GIVE AN UPDATE SO I WILL BE ABLE TO DO A FINAL WALK THROUGH AND ISSUE PERMIT. 
Facility matched [view inspection report] [update / view this inspection] [add reinspection]
COMPLIED Facility Id:AE43662 Facility Name:RODEHEAVER AUDITORIUM/ GYM
Inspection Date: 05/10/2016 Inspection Status: COMPLIED ;Inspection Type: Reinspection
Inspector: ED SORENSEN ;Record Created Date:05/10/2016
Sprinkler:   Alarm: G  Remarks:WENT TO FACILITY TO REVIEW REQUESTED PAPERWORK. IT WAS PROVIDED AND I COMPLIED THE ORIGINAL INSPECTION HOWEVER I NEED TO RETURN AFTER ALL RENOVATIONS ARE COMPLETED TO DO A FINAL INSPECTION AND THEN ISSUE THE AE PERMIT. 
Facility matched [view inspection report] [update / view this inspection] [add reinspection]
Facility Id:AE43662 Facility Name:RODEHEAVER AUDITORIUM/ GYM
Inspection Date: 05/02/2016 Inspection Status: VIOLATION ;Inspection Type: Reinspection
Inspector: ED SORENSEN ;Record Created Date:05/02/2016
Remarks:KOORSEN JUST DID THE ANNUAL INSPECTION AND THEY WILL SEND THEM A REPORT WITHIN THE NEXT COUPLE OF DAYS.I STILL NEED TO REINSPECT AFTER RENOVATIONS ARE COMPLETED. 
Facility matched [view inspection report] [update / view this inspection] [add reinspection] [violation order]
Facility Id:AE43662 Facility Name:RODEHEAVER AUDITORIUM/ GYM
Inspection Date: 04/11/2016 Inspection Status: VIOLATION ;Inspection Type: Reinspection
Inspector: ED SORENSEN ;Record Created Date:04/11/2016
Remarks:STILL NEED FIRE ALARM REPORT AND NEED TO INSPECT AFTER REMODELING IS COMPLETED. 
[view inspection report] [update / view this inspection] [add reinspection] [violation order]
Facility Id:AE43662 Facility Name:RODEHEAVER AUDITORIUM/ GYM
Inspection Date: 02/24/2016 Inspection Status: VIOLATION ;Inspection Type: Annual
Inspector: ED SORENSEN ;Record Created Date:02/24/2016
Remarks:NOTE: INSPECTED WITH GLENN GOLDSMITH. THIS BUILDING IS BEING LEASED OUT AND IS UNDERGOING REMODELING. I NEED TO REINSPECT BUILDING AFTER REMODELING HAS BEEN COMPLETED. 
Facility matched [view inspection report] [update / view this inspection] [add reinspection] [violation order]
COMPLIED Facility Id:AE43662 Facility Name:RODEHEAVER AUDITORIUM/ GYM
Inspection Date: 03/16/2015 Inspection Status: COMPLIED ;Inspection Type: Reinspection
Inspector: ED SORENSEN ;Record Created Date:03/16/2015
Sprinkler:   Alarm: G  Remarks: 
Facility matched [view inspection report] [update / view this inspection] [add reinspection]
Facility Id:AE43662 Facility Name:RODEHEAVER AUDITORIUM/ GYM
Inspection Date: 02/16/2015 Inspection Status: VIOLATION ;Inspection Type: Reinspection
Inspector: ED SORENSEN ;Record Created Date:02/16/2015
Remarks:Reinspected. Violations not all corrected. Gave 30 more days. 
[view inspection report] [update / view this inspection] [add reinspection] [violation order]
Facility Id:AE43662 Facility Name:RODEHEAVER AUDITORIUM/ GYM
Inspection Date: 01/14/2015 Inspection Status: VIOLATION ;Inspection Type: Documentation only
Inspector: ED SORENSEN ;Record Created Date:01/14/2015
Remarks:UPDATE-PER NOTICE FROM OFFICE THE AE PERMIT WAS APPLIED FOR. THEY DO NOT NEED TO REAPPLY AT THIS TIME. DOCUMENTATION ONLY. NOT A SITE VISIT. 
Facility matched [view inspection report] [update / view this inspection] [add reinspection] [violation order]
Facility Id:AE43662 Facility Name:RODEHEAVER AUDITORIUM/ GYM
Inspection Date: 01/13/2015 Inspection Status: VIOLATION ;Inspection Type: Annual
Inspector: ED SORENSEN ;Record Created Date:01/13/2015
Remarks:Inspected with Glenn Goldsmith. 
Facility matched [view inspection report] [update / view this inspection] [add reinspection] [violation order]
COMPLIED Facility Id:AE43662 Facility Name:RODEHEAVER AUDITORIUM/ GYM
Inspection Date: 02/13/2014 Inspection Status: COMPLIED ;Inspection Type: Annual
Inspector: GEARALD PUFFER ;Record Created Date:02/13/2014
Sprinkler: G  Alarm: G  Remarks: 
Facility matched [view inspection report] [update / view this inspection] [add reinspection]
NOTES Facility Id:AE43662 Facility Name:RODEHEAVER AUDITORIUM/ GYM
Inspection Date: 08/14/2013 Inspection Status: NOTES ;Inspection Type: Site Visit
Inspector: ED SORENSEN ;Record Created Date:08/14/2013
Sprinkler:   Alarm:   Remarks:While in Warsaw, I drove by nearby Winona Lake to this building. Before attempting to go in, I checked the data base and see that this building was inspected earlier this year under #AE43662. I am checking with Chris to try to consolidate all applicable AE numbers. Update note: I called Jim Straws and Glen Goldsmith and found that the current AE numbers for this building should all be under AE43662. Requested applicable numbers to be consolidated. 
[view inspection report] [update / view this inspection] [add reinspection]
NOTES Facility Id:AE43662 Facility Name:RODEHEAVER AUDITORIUM/ GYM
Inspection Date: 07/24/2013 Inspection Status: NOTES ;Inspection Type: Site Visit
Inspector: ED SORENSEN ;Record Created Date:07/24/2013
Sprinkler:   Alarm:   Remarks:Visited site. The doors were locked and I made 2 phone calls and left a voice message to request an appointment to do the inspection. To followup. 
Facility matched [view inspection report] [update / view this inspection] [add reinspection]
COMPLIED Facility Id:AE43662 Facility Name:RODENHEAVER AUDITORIUM
Inspection Date: 03/20/2013 Inspection Status: COMPLIED ;Inspection Type: Reinspection
Inspector: JAMES STRAWS ;Record Created Date:03/20/2013
Sprinkler:   Alarm: G  Remarks:Inspection was made with Glen Goldsmith 
Facility matched [view inspection report] [update / view this inspection] [add reinspection]
Facility Id:AE43662 Facility Name:RODENHEAVER AUDITORIUM
Inspection Date: 01/29/2013 Inspection Status: VIOLATION ;Inspection Type: Annual
Inspector: JAMES STRAWS ;Record Created Date:01/29/2013
Remarks:Inspection was made with Zack Smith 
Facility matched [view inspection report] [update / view this inspection] [add reinspection] [violation order]
C Facility Id:AE43662 Facility Name:
Inspection Date: 10/13/2009 Inspection Status: C ;Inspection Type: RE-INSPECTION
Inspector: MARK SHAVER ;Record Created Date:
Sprinkler: N  Alarm: Y  Remarks: 
Facility Id:AE43662 Facility Name:
Inspection Date: 09/24/2009 Inspection Status: F ;Inspection Type: ANNUAL
Inspector: MARK SHAVER ;Record Created Date:
Remarks:3 part violations FA testing, open splice, missing elec covers 
C Facility Id:AE43662 Facility Name:
Inspection Date: 04/18/2007 Inspection Status: C ;Inspection Type: ANNUAL
Inspector: MIKE FISHER ;Record Created Date:
Sprinkler: N  Alarm: Y  Remarks:COMPLIED. 
C Facility Id:AE43662 Facility Name:
Inspection Date: 04/18/2007 Inspection Status: C ;Inspection Type: ANNUAL
Inspector: MIKE FISHER ;Record Created Date:
Sprinkler: N  Alarm: Y  Remarks:COMPLIED. 
C Facility Id:AE43662 Facility Name:
Inspection Date: 10/26/2006 Inspection Status: C ;Inspection Type: RE-INSPECTION
Inspector: MIKE FISHER ;Record Created Date:
Sprinkler: N  Alarm: Y  Remarks: 
C Facility Id:AE43662 Facility Name:
Inspection Date: 10/26/2006 Inspection Status: C ;Inspection Type: RE-INSPECTION
Inspector: MIKE FISHER ;Record Created Date:
Sprinkler: N  Alarm: Y  Remarks: 
Facility Id:AE43662 Facility Name:
Inspection Date: 05/30/2006 Inspection Status: V ;Inspection Type: ANNUAL
Inspector: MIKE FISHER ;Record Created Date:
Remarks: 
[violation order]
C Facility Id:AE43662 Facility Name:
Inspection Date: 05/30/2006 Inspection Status: C ;Inspection Type: ANNUAL
Inspector: MIKE FISHER ;Record Created Date:
Sprinkler: N  Alarm: Y  Remarks: 
Facility Id:AE43662 Facility Name:
Inspection Date: 05/10/2005 Inspection Status: V ;Inspection Type: ANNUAL
Inspector: MIKE FISHER ;Record Created Date:
Remarks: 
[violation order]
C Facility Id:AE43662 Facility Name:
Inspection Date: 05/10/2005 Inspection Status: C ;Inspection Type: REINSPECTION
Inspector: MIKE FISHER ;Record Created Date:
Sprinkler: N  Alarm: Y  Remarks: 
C Facility Id:AE43662 Facility Name:
Inspection Date: 08/06/2004 Inspection Status: C ;Inspection Type: REINSPECTION
Inspector: MIKE FISHER ;Record Created Date:
Sprinkler: N  Alarm: Y  Remarks: 
C Facility Id:AE43662 Facility Name:
Inspection Date: 08/06/2004 Inspection Status: C ;Inspection Type: REINSPECTION
Inspector: MIKE FISHER ;Record Created Date:
Sprinkler: N  Alarm: Y  Remarks: 
Facility Id:AE43662 Facility Name:
Inspection Date: 05/12/2004 Inspection Status: V ;Inspection Type: ANNUAL INSPECTION
Inspector: MIKE FISHER ;Record Created Date:
Remarks: 
[violation order]
Facility Id:AE43662 Facility Name:
Inspection Date: 05/12/2004 Inspection Status: V ;Inspection Type: ANNUAL INSPECTION
Inspector: MIKE FISHER ;Record Created Date:
Remarks: 
[violation order]
C Facility Id:AE43662 Facility Name:
Inspection Date: 05/01/2003 Inspection Status: C ;Inspection Type:
Inspector: MIKE FISHER ;Record Created Date:
Sprinkler: N  Alarm: Y  Remarks: 
C Facility Id:AE43662 Facility Name:
Inspection Date: 05/01/2003 Inspection Status: C ;Inspection Type:
Inspector: MIKE FISHER ;Record Created Date:
Sprinkler: Y  Alarm: Y  Remarks: 
Facility Id:AE43662 Facility Name:
Inspection Date: 03/04/2003 Inspection Status: V ;Inspection Type: ANNUAL INSPECTION
Inspector: MIKE FISHER ;Record Created Date:
Remarks: 
[violation order]
Facility Id:AE43662 Facility Name:
Inspection Date: 03/04/2003 Inspection Status: V ;Inspection Type: ANNUAL INSPECTION
Inspector: MIKE FISHER ;Record Created Date:
Remarks: 
[violation order]
C Facility Id:AE43662 Facility Name:
Inspection Date: 08/29/2002 Inspection Status: C ;Inspection Type: RE-INSPECTION
Inspector: MIKE FISHER ;Record Created Date:
Sprinkler: N  Alarm: Y  Remarks: 
Facility Id:AE43662 Facility Name:
Inspection Date: 04/08/2002 Inspection Status: V ;Inspection Type:
Inspector: MIKE FISHER ;Record Created Date:
Remarks: 
[violation order]
C Facility Id:AE43662 Facility Name:
Inspection Date: 04/08/2002 Inspection Status: C ;Inspection Type: ANNUAL INSPECITON
Inspector: MIKE FISHER ;Record Created Date:
Sprinkler: N  Alarm: Y  Remarks: 
C Facility Id:AE43662 Facility Name:
Inspection Date: 07/05/2001 Inspection Status: C ;Inspection Type:
Inspector: MIKE FISHER ;Record Created Date:
Sprinkler: N  Alarm: Y  Remarks: 
C Facility Id:AE43662 Facility Name:
Inspection Date: 04/10/2001 Inspection Status: C ;Inspection Type: ANNUAL INSPECTION
Inspector: MIKE FISHER ;Record Created Date:
Sprinkler: N  Alarm: Y  Remarks: 
Facility Id:AE43662 Facility Name:
Inspection Date: 04/10/2001 Inspection Status: V ;Inspection Type:
Inspector: MIKE FISHER ;Record Created Date:
Remarks: 
[violation order]
C Facility Id:AE43662 Facility Name:
Inspection Date: 09/07/2000 Inspection Status: C ;Inspection Type: RE-INSPECTION
Inspector: MIKE FISHER ;Record Created Date:
Sprinkler: Y  Alarm: Y  Remarks: 
Facility Id:AE43662 Facility Name:
Inspection Date: 06/07/2000 Inspection Status: V ;Inspection Type: ANNUAL
Inspector: MIKE FISHER ;Record Created Date:
Remarks: 
[violation order]
C Facility Id:AE43662 Facility Name:
Inspection Date: 05/30/2000 Inspection Status: C ;Inspection Type: RE-INSPECTION
Inspector: MIKE FISHER ;Record Created Date:
Sprinkler: N  Alarm: Y  Remarks: 
Facility Id:AE43662 Facility Name:
Inspection Date: 04/12/2000 Inspection Status: V ;Inspection Type: ANNUAL
Inspector: MIKE FISHER ;Record Created Date:
Remarks: 
[violation order]
Facility Id:AE43662 Facility Name:
Inspection Date: 06/25/1999 Inspection Status: V ;Inspection Type: RE-INSPECTION
Inspector: MIKE FISHER ;Record Created Date:
Remarks: 
[violation order]
Facility Id:AE43662 Facility Name:
Inspection Date: 06/03/1999 Inspection Status: V ;Inspection Type: ANNUAL
Inspector: DEBORAH FRYE ;Record Created Date:
Remarks:NOTE ONLY: AN ATTEMPT TO INSPECT WAS MADE 06/03/99, APPROXIMATELY 2:00 PM. NO ACCESS. 
[violation order]
 
 
 

Inspector Activity:

activity Type activity date activity duration contact location remarks Inspector