Record Created Date: 01/09/2019
* facility ID:
* facility name:
* facility street number:
* facility street prefix:
* facility street name:
* facility street suffix:
facility address2:
* facility city:
* facility county:
facility state: IN
* facility zip:
* facility contact:
* facility telephone:
* facility Email:
Foundation/Footer status:
Concrete Slab status:
Framing Status:
Plumbing status:
Mechanical status:
Electrical status:
Energy status:
Sprinkler status:
alarm status:
sensitivity current :
Interior status:
Pool status:
Egress status:
Suppression status:
temporary indoor stage:
temporary outdoor stage:
outdoor stage equipment :
canopy:
tent :
ust installation:
ust removal:
project Type(select ll that apply): New: Addition: Remodel: Occ.Change: Existing:
inspection Category:
inspection type:
inspection status:
inspection Date: (mm/dd/yyyy)Pick a date
violation to be corrected by Date: (mm/dd/yyyy)Pick a date
* inspector:
notes:
Facility Match?: (Type in Facility Matched, when you match a complaint inspection with facility.)
[view & print annual permit] [Email permit]
print order code description remarks violation to be corrected by date violation complied date

IC 22-14-3-5 
Operation without permit or special event endorsement; infraction Sec. 5. (a) This section applies to the following: (1) Each person who has control over the performance of an amusement or entertainment described in IC 22-12-1-23. (2) Each person who has control over a regulated place of entertainment. (b) A person described in subsection (a) commits a Class C infraction if: (1) a regulated place of amusement or entertainment is used for an amusement or entertainment described in IC 22-12-1-23; and (2) no regulated place of amusement or entertainment permit or special event endorsement issued under this chapter covers the conditions at the regulated place of amusement or entertainment that affect fire and explosion safety.  
Amusement and Entertainment permit expires 1-10-2019. 
02/08/2019 
 

Sec. 406.2 2014 Edition IFC 675 IAC 22-2.5 
Employees shall receive training in the contents of fire safety and evacuation plans and their duties as part of new employee orientation and at least annually thereafter. Records shall be kept and made available to the fire code official upon request. 
Current Fire/Safety training documentation could not be provided.  
02/08/2019 
 

Sec. 404.2 2014 Edition IFC 675 IAC 22-2.5 
An approved fire safety and evacuation plan shall be prepared and maintained for the following occupancies and buildings. 1. Group A, other than Group A occupancies used exclusively for purposes of religious worship that have an occupant load less than 2,000. 2. Group B buildings having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge. 3. Group E. 4. Group F buildings having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge. 5. Group H. 6. Group I. 7. Group R-1. 8. Group R-2 college and university buildings. 9. Group R-4. 10. High-rise buildings. 11. Group M buildings having an occupant load of 500 or more persons or more than 100 persons above or below the lowest level of exit discharge. 12. Covered malls exceeding 50,000 square feet (4645 m2) in aggregate floor area. 13. Open mall buildings exceeding 50,000 square feet (4645 m2) in aggregate area within perimeter line. 14. Underground buildings. 15. Buildings with an atrium and having an occupancy in Group A, E or M. 
Current evacuation plan was not available on site.  
02/08/2019 
 

Sec. 405.5 2014 Edition IFC 675 IAC 22-2.5 
Records shall be maintained of required emergency evacuation drills and include the following information: 1. Identity of the person conducting the drill. 2. Date and time of the drill. 3. Notification method used. 4. Staff members on duty and participating. 5. Number of occupants evacuated. 6. Special conditions simulated. 7. Problems encountered. 8. Weather conditions when occupants were evacuated. 9. Time required to accomplish complete evacuation. 
Current quarterly, employee only, evacuation drill documentation could not be provided.  
02/08/2019 
 

Sec. 1030.2 2014 Edition IFC 675 IAC 22-2.5 
Required exit accesses, exits and exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the building area served by the means of egress is occupied. An exit or exit passageway shall not be used for any purpose that interferes with a means of egress. 
Rear exit is obstructed. 
02/08/2019 
 

Sec. 605.4.2 2014 Edition IFC 675 IAC 22-2.5 
Relocatable power taps shall be directly connected to a permanently installed receptacle. 
Power taps are piggy backed in Office. 
02/08/2019 
 

Sec. 605.9 2014 Edition IFC 675 IAC 22-2.5 
Temporary wiring for electrical power and lighting installations is allowed for a period not to exceed 90 days. Temporary wiring methods shall meet the applicable provisions of NFPA 70. Exception: Temporary wiring for electrical power and lighting installations is allowed during periods of construction, remodeling, repair or demolition of buildings, structures, equipment or similar activities. 
Entry has temporary light installation that has exceeded 90 days. 
02/08/2019 
 

Sec. 1030.2.1 2014 Edition IFC  675 IAC 22-2.5 
Security devices and egress locks. Security devices affecting means of egress shall be approved by the fire code official. Special locking arrangements including, but not limited to access-controlled egress doors, security grills, locks and latches, and delayed egress locks shall be installed and maintained as required by this chapter. 
Back exit door has a latch type lock.  
02/08/2019