Record Created Date: 11/28/2018
* facility ID:
* facility name:
* facility street number:
* facility street prefix:
* facility street name:
* facility street suffix:
facility address2:
* facility city:
* facility county:
facility state: IN
* facility zip:
* facility contact:
* facility telephone:
* facility Email:
Foundation/Footer status:
Concrete Slab status:
Framing Status:
Plumbing status:
Mechanical status:
Electrical status:
Energy status:
Sprinkler status:
alarm status:
sensitivity current :
Interior status:
Pool status:
Egress status:
Suppression status:
temporary indoor stage:
temporary outdoor stage:
outdoor stage equipment :
canopy:
tent :
ust installation:
ust removal:
project Type(select ll that apply): New: Addition: Remodel: Occ.Change: Existing:
inspection Category:
inspection type:
inspection status:
inspection Date: (mm/dd/yyyy)Pick a date
violation to be corrected by Date: (mm/dd/yyyy)Pick a date
* inspector:
notes:
Facility Match?: (Type in Facility Matched, when you match a complaint inspection with facility.)
[view & print annual permit] [Email permit]
print order code description remarks violation to be corrected by date violation complied date

Sec. 901.6.2 2014 Edition IFC 675 IAC 22-2.5 
Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises or made readily available for a minimum of two (2) years from the date of the last inspection, except that original acceptance test reports shall be maintained for the life of the system. 
The last two years of documentation was not available for the following systems: Fire alarm, bi-annual sensitivity test. Without the proper documentation it can not be ascertained if the system is being maintained in accordance with the standards and is in operable conditions at all times. 
12/12/2018 
 

Sec. 5.2.2.2 2002 Edition NFPA 25 675 IAC 28-1-12 
Sprinkler piping shall not be subjected to external loads by materials either resting on the pipe or hung from the pipe. 
Sprinkler pipe in camera room has data cable attached and camera wire ran through pipe supports. 
12/12/2018 
 

Sec. 315.3.1 2014 Edition IFC 675 IAC 22-2.5 
Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. Exception: Sidewall storage to a maximum depth of thirty (30) inches (seventy-six and two-tenths (76.2) centimeters) shall be acceptable to the ceiling in nonsprinklered buildings. 
Storage to close to sprinklers in closet under stairs. 
12/12/2018 
 

Sec. 408.7 2009 Edition IEC  
Unused openings for circuit breakers and switches shall be closed using identified closures, or other approved means that provide protection substantially equivalent to the wall of the enclosure.  
Open circuit breaker slots in panel A. 
12/12/2018