DHS

Indiana Department of Homeland Security / Fire and Building Safety Division

2020-21 version

 

Update Inspection

[Open Report in Chrome Browser]
[back to inspection list]
[view and Print Report (No Notes)]
[view and Print Report with Notes]
__________________________
Record Created Date: 11/26/2018
* facility ID:
* facility name:
* facility street number:
* facility street prefix:
* facility street name:
* facility street suffix:
facility address2:
* facility city:
* facility county:
facility state: IN
* facility zip:
* facility contact:
* facility telephone:
* facility Email:
Foundation/Footer status:
Concrete Slab status:
Framing Status:
Plumbing status:
Mechanical status:
Electrical status:
Energy status:
Sprinkler status:
alarm status:
sensitivity current :
Interior status:
Pool status:
Egress status:
Suppression status:
temporary indoor stage:
temporary outdoor stage:
outdoor stage equipment :
canopy:
tent :
ust installation:
ust removal:
project Type(select ll that apply): New: Addition: Remodel: Occ.Change: Existing:
inspection Category:
inspection type:
inspection status:
inspection Date: (mm/dd/yyyy)Pick a date
violation to be corrected by Date: (mm/dd/yyyy)Pick a date
* inspector:
notes:
Facility Match?: (Type in Facility Matched, when you match a complaint inspection with facility.)
[view & print annual permit] [Email permit]
print order code description remarks violation to be corrected by date violation complied date

IC 22-14-3-5 
Operation without permit or special event endorsement; infraction Sec. 5. (a) This section applies to the following: (1) Each person who has control over the performance of an amusement or entertainment described in IC 22-12-1-23. (2) Each person who has control over a regulated place of entertainment. (b) A person described in subsection (a) commits a Class C infraction if: (1) a regulated place of amusement or entertainment is used for an amusement or entertainment described in IC 22-12-1-23; and (2) no regulated place of amusement or entertainment permit or special event endorsement issued under this chapter covers the conditions at the regulated place of amusement or entertainment that affect fire and explosion safety.  
The facilities annual A&E permit is expired. 
12/26/2018 
 

Sec. 901.6.2 2014 Edition IFC 675 IAC 22-2.5 
Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises or made readily available for a minimum of two (2) years from the date of the last inspection, except that original acceptance test reports shall be maintained for the life of the system. 
Copies of the hood suppression and fire alarm inspection reports could not be provided at the time of inspection. 
12/26/2018 
 

Sec. 1008.1.9 2014 Edition IFC 675 IAC 22-2.5 
Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 
A hasp and pad lock and flush bolt were found on the doors leading into the two storage rooms in the banquet room. 
12/26/2018 
 

Sec. 5303.5.3 2014 Edition IFC 675 IAC 22-2.5 
Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints. 2. Securing containers, cylinders and tanks on a cart or other mobile device designed for the movement of compressed gas containers, cylinders or tanks. 3. Nesting of compressed gas containers, cylinders and tanks at container filling or servicing facilities or in seller?s warehouses not accessible to the public. Nesting shall be allowed provided the nested containers, cylinders or tanks, if dislodged, do not obstruct the required means of egress. 4. Securing of compressed gas containers, cylinders and tanks to or within a rack, framework, cabinet or similar assembly designed for such use. Exception: Compressed gas containers, cylinders and tanks in the process of examination, filling, transport or servicing. 
A compressed gas cylinder was found unsecured in the kitchen. 
12/26/2018