Indiana Department of Homeland Security / Fire and Building Safety Division

2020-21 version

 

Update Inspection

[Open Report in Chrome Browser]
[back to inspection list]
[view and Print Report (No Notes)]
[view and Print Report with Notes]
__________________________
Record Created Date: 08/16/2016
* facility ID:
* facility name:
* facility street number:
* facility street prefix:
* facility street name:
* facility street suffix:
facility address2:
* facility city:
* facility county:
facility state: IN
* facility zip:
* facility contact:
* facility telephone:
* facility Email:
Foundation/Footer status:
Concrete Slab status:
Framing Status:
Plumbing status:
Mechanical status:
Electrical status:
Energy status:
Sprinkler status:
alarm status:
sensitivity current :
Interior status:
Pool status:
Egress status:
Suppression status:
temporary indoor stage:
temporary outdoor stage:
outdoor stage equipment :
canopy:
tent :
ust installation:
ust removal:
project Type(select ll that apply): New: Addition: Remodel: Occ.Change: Existing:
inspection Category:
inspection type:
inspection status:
inspection Date: (mm/dd/yyyy)Pick a date
violation to be corrected by Date: (mm/dd/yyyy)Pick a date
* inspector:
notes:
Facility Match?: (Type in Facility Matched, when you match a complaint inspection with facility.)
[view & print annual permit] [Email permit]
print order code description remarks violation to be corrected by date violation complied date

IC 22-14-3-5 
Operation without permit or special event endorsement; infraction Sec. 5. (a) This section applies to the following: (1) Each person who has control over the performance of an amusement or entertainment described in IC 22-12-1-23. (2) Each person who has control over a regulated place of entertainment. (b) A person described in subsection (a) commits a Class C infraction if: (1) a regulated place of amusement or entertainment is used for an amusement or entertainment described in IC 22-12-1-23; and (2) no regulated place of amusement or entertainment permit or special event endorsement issued under this chapter covers the conditions at the regulated place of amusement or entertainment that affect fire and explosion safety.  
The facility, which is renting a portion of the area for weddings and similar events, has not renewed their Amusement and Entertainment permit. 
09/16/2016 
 

Sec. 604.5.2 2014 Edition IFC 675 IAC 22-2.5 
For battery-powered emergency lighting, a power test of the emergency lighting equipment shall be completed annually. The power test shall operate the emergency lighting for a minimum of 90 minutes and shall remain sufficiently illuminated for the duration of the test. 
Documentation could not be provided to show that the annual 90 minute load testing has been performed. 
09/16/2016 
 

Sec. 507.12 2014 Edition IMC 675 IAC 18-1.6 
The inside lower edge of canopy-type Type I and II commercial hoods shall overhang or extend a horizontal distance of not less than 6 inches (152 mm) beyond the edge of the top horizontal surface of the appliance on all open sides. The vertical distance between the front lower lip of the hood and such surface shall not exceed 4 feet (1219 mm). Exception: The hood shall be permitted to be flush with the outer edge of the cooking surface where the hood is closed to the appliance side by a noncombustible wall or panel. 
A large 8 burner range has been added and the appropriate hood overhang is no longer being provided. 
09/16/2016 
 

Sec. 5303.5.3 2014 Edition IFC 675 IAC 22-2.5 
Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following methods: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints. 2. Securing containers, cylinders and tanks on a cart or other mobile device designed for the movement of compressed gas containers, cylinders or tanks. 3. Nesting of compressed gas containers, cylinders and tanks at container filling or servicing facilities or in seller?s warehouses not accessible to the public. Nesting shall be allowed provided the nested containers, cylinders or tanks, if dislodged, do not obstruct the required means of egress. 4. Securing of compressed gas containers, cylinders and tanks to or within a rack, framework, cabinet or similar assembly designed for such use. Exception: Compressed gas containers, cylinders and tanks in the process of examination, filling, transport or servicing. 
Compressed gas cylinders located in the banquet drink room were found not being properly secured. 
09/16/2016 
 

Sec. 1008.1.9.4 2014 Edition IFC 675 IAC 22-2.5 
Manually operated flush bolts or surface bolts are not permitted. Exceptions: 1. On doors not required for egress in individual dwelling units or sleeping units. 2. Where a pair of doors serves a storage or equipment room, manually operated edge- or surface-mounted bolts are permitted on the inactive leaf. 3. Where a pair of doors serves an occupant load of less than 50 persons in a Group B, F or S occupancy, manually operated edge- or surface- mounted bolts are permitted on the inactive leaf. The inactive leaf shall contain no doorknobs, panic bars or similar operating hardware. 4. Where a pair of doors serves a Group B, F or S occupancy, manually operated edge- or surface- mounted bolts are permitted on the inactive leaf provided such inactive leaf is not needed to meet egress width requirements and the building is equipped throughout with an automatic sprinkler system in accordance with Section 903.3.1.1. The inactive leaf shall contain no doorknobs, panic bars or similar operating hardware. 5. Where a pair of doors serves patient care rooms in Group I-2 occupancies, self-latching edge- or surface-mounted bolts are permitted on the inactive leaf provided that the inactive leaf is not needed to meet egress width requirements and the inactive leaf contains no doorknobs, panic bars or similar operating hardware. 
Flush bolt locks were found installed on the doors in the center corridor and shall be removed. 
09/16/2016 
 

Sec. 806.2 2014 Edition IFC 675 IAC 22-2.5 
Artificial decorative vegetation shall meet the flame propagation performance criteria of NFPA 701. Meeting the flame propagation performance criteria of NFPA 701 shall be documented and certified by the manufacturer in an approved manner. Alternatively, the artificial decorative vegetation item shall be tested in accordance with NFPA 289, using the 20 kW ignition source, and shall have a maximum heat release rate of 100 kW. 
Artificial vegetation was observed in the billiard room, however, documentation could not be provide to show that it meets the flame propagation requirements of NFPA 701. 
09/16/2016 
 

Sec. 605.5 2014 Edition IFC 675 IAC 22-2.5 
Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. 
Extension cords, located above the pool table and the East TV in the banquet room were found passing through the ceiling and shall be removed. 
09/16/2016