__________________________
Record Created Date: 01/06/2016
* facility ID:
* facility name:
* facility street number:
* facility street prefix:
* facility street name:
* facility street suffix:
facility address2:
* facility city:
* facility county:
facility state: IN
* facility zip:
* facility contact:
* facility telephone:
* facility Email:
Foundation/Footer status:
Concrete Slab status:
Framing Status:
Plumbing status:
Mechanical status:
Electrical status:
Energy status:
Sprinkler status:
alarm status:
sensitivity current :
Interior status:
Pool status:
Egress status:
Suppression status:
temporary indoor stage:
temporary outdoor stage:
outdoor stage equipment :
canopy:
tent :
ust installation:
ust removal:
project Type(select ll that apply): New: Addition: Remodel: Occ.Change: Existing:
inspection Category:
inspection type:
inspection status:
inspection Date: (mm/dd/yyyy)Pick a date
violation to be corrected by Date: (mm/dd/yyyy)Pick a date
* inspector:
notes:
Facility Match?: (Type in Facility Matched, when you match a complaint inspection with facility.)
[view & print annual permit] [Email permit]
print order code description remarks violation to be corrected by date violation complied date

675 IAC 12-9-3 
675 IAC 12-9-3 Amusement and entertainment permits Sec. 3. (a) An applicant for an annual amusement and entertainment permit shall submit an application, with the applicable fee as set in IC 22-12-6-7, to the state fire marshal on forms provided by the division. An application may be submitted as early as September 1 of the year preceding the calendar year for which a permit will cover. Each application shall provide the information required by IC 22-14-3-3 and the following: (1) A listing of each use, giving the: (A) days and hours of operation of regularly scheduled events; and (B) dates and inclusive times of special events planned to be conducted; in the calendar year for which a permit is to cover. (2) An attached floor plan or site plan showing the following: (A) The planned arrangement of other than fixed seating. (B) The location of the following: (i) Aisles. (ii) Exit ways. (iii) Barriers. (iv) Steps. (v) Other crowd movement or control facilities, equipment, signs, or personnel. (3) The maximum occupancy intended for both seated and standing attendees. (4) The name, address, and telephone number of the person to be contacted to arrange for inspections by the state fire marshal. (b) An applicant for a special event endorsement to an annual amusement and entertainment permit shall submit an application to the state fire marshal on forms provided by the division. Each application shall provide the following information: (1) The permit number and address of the regulated place of amusement or entertainment for which an endorsement is sought. (2) The name, address, and telephone number of the applicant if different than the applicant for the annual permit. (3) The additional use, dates, and times of a special event not covered in the annual permit. (4) An additional floor or site plan for the special event if different than the plans submitted with the application for the annual permit. (5) The maximum occupancy intended for both seated and standing attendees. (c) A permit issued under IC 22-14-3-2 and this section expires on December 31 in the year it is issued.  
Reminder that your annual entertainment permit expires next month and will need to be renewed. 
02/08/2016 
 

Sec. 609.3.3.3 2014 Edition IFC 675 IAC 22-2.5 
Records for inspections shall state the individual and company performing the inspection, a description of the inspection and when the inspection took place. Records for cleanings shall state the individual and company performing the cleaning and when the cleaning took place. Such records shall be completed after each inspection or cleaning, maintained on the premises for a minimum of three years and be copied to the fire code official upon request. 
Provide copy of the most recent inspection/cleaning of the kitchen exhaust system. 
02/08/2016 
 

Sec. 1006.1 2014 Edition IFC 675 IAC 22-2.5 
The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. Exceptions: 1. Occupancies in Group U. 2. Aisle accessways in Group A. 3. Dwelling units and sleeping units in Groups R-1, R-2 and R-3. 4. Sleeping units of Group I occupancies 
Repair south east emergency light/exit sign to proper operation as it did not light up when test button was pushed.  
02/08/2016 
 

Sec. 703.1 2014 Edition IFC 675 IAC 22-2.5 
The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be visually inspected by the owner annually and properly repaired, restored or replaced when damaged, altered, breached or penetrated. Where concealed, such elements shall not be required to be visually inspected by the owner unless the concealed space is accessible by the removal or movement of a panel, access door, ceiling tile or similar movable entry to the space. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. Openings through fire-resistance-rated assemblies shall be protected by self- or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. 
Provide firestopping with approved firestopping method around water heater flue at ceiling tile. 
02/08/2016