__________________________
Record Created Date: 11/17/2015
* facility ID:
* facility name:
* facility street number:
* facility street prefix:
* facility street name:
* facility street suffix:
facility address2:
* facility city:
* facility county:
facility state: IN
* facility zip:
* facility contact:
* facility telephone:
* facility Email:
Foundation/Footer status:
Concrete Slab status:
Framing Status:
Plumbing status:
Mechanical status:
Electrical status:
Energy status:
Sprinkler status:
alarm status:
sensitivity current :
Interior status:
Pool status:
Egress status:
Suppression status:
temporary indoor stage:
temporary outdoor stage:
outdoor stage equipment :
canopy:
tent :
ust installation:
ust removal:
project Type(select ll that apply): New: Addition: Remodel: Occ.Change: Existing:
inspection Category:
inspection type:
inspection status:
inspection Date: (mm/dd/yyyy)Pick a date
violation to be corrected by Date: (mm/dd/yyyy)Pick a date
* inspector:
notes:
Facility Match?: (Type in Facility Matched, when you match a complaint inspection with facility.)
[view & print annual permit] [Email permit]
print order code description remarks violation to be corrected by date violation complied date

Sec. 901.6.2 2014 Edition IFC 675 IAC 22-2.5 
Records of all system inspections, tests and maintenance required by the referenced standards shall be maintained on the premises or made readily available for a minimum of two (2) years from the date of the last inspection, except that original acceptance test reports shall be maintained for the life of the system. 
A copy of the most recent alarm inspection report could not be provided as required. 
12/17/2015 
 

Sec. 604.5.2 2014 Edition IFC 675 IAC 22-2.5 
For battery-powered emergency lighting, a power test of the emergency lighting equipment shall be completed annually. The power test shall operate the emergency lighting for a minimum of 90 minutes and shall remain sufficiently illuminated for the duration of the test. 
The required emergency/exit light testing has not been completed and documented as required. 
12/17/2015 
 

Sec. 404.3.1 2014 Edition IFC 675 IAC 22-2.5 
Fire evacuation plans shall include the following: 1. Emergency egress or escape routes and whether evacuation of the building is to be complete or, where approved, by selected floors or areas only. 2. Procedures for employees who must remain to operate critical equipment before evacuating. 3. Procedures for assisted rescue for persons unable to use the general means of egress unassisted. 4. Procedures for accounting for employees and occupants after evacuation has been completed. 5. Identification and assignment of personnel responsible for rescue or emergency medical aid. 6. The preferred and any alternative means of notifying occupants of a fire or emergency. 7. The preferred and any alternative means of reporting fires and other emergencies to the fire department or designated emergency response organization. 8. Identification and assignment of personnel who can be contacted for further information or explanation of duties under the plan. 9. A description of the emergency voice/alarm communication system alert tone and preprogrammed voice messages, where provided. 
The required fire evacuation plan shall include all applicable items as listed. 
12/17/2015 
 

Sec. 404.3.2 2014 Edition IFC 675 IAC 22-2.5 
Fire safety plans shall include the following: 1. The procedure for reporting a fire or other emergency. 2. The life safety strategy and procedures for notifying, relocating or evacuating occupants, including occupants who need assistance. 3. Site plans indicating the following: 3.1. The occupancy assembly point. 3.2. The locations of fire hydrants. 3.3. The normal routes of fire department vehicle access. 4. Floor plans identifying the locations of the following: 4.1. Exits. 4.2. Primary evacuation routes. 4.3. Secondary evacuation routes. 4.4. Accessible egress routes. 4.5. Areas of refuge. 4.6. Exterior areas for assisted rescue. 4.7. Manual fire alarm boxes. 4.8. Portable fire extinguishers. 4.9. Occupant-use hose stations. 4.10. Fire alarm annunciators and controls. 5. A list of major fire hazards associated with the normal use and occupancy of the premises, including maintenance and housekeeping procedures. 6. Identification and assignment of personnel responsible for maintenance of systems and equipment installed to prevent or control fires. 7. Identification and assignment of personnel responsible for maintenance, housekeeping and controlling fuel hazard sources. 
The required fire safety plan shall include all applicable items as listed. 
 
 

Sec. 406.2 2014 Edition IFC 675 IAC 22-2.5 
Employees shall receive training in the contents of fire safety and evacuation plans and their duties as part of new employee orientation and at least annually thereafter. Records shall be kept and made available to the fire code official upon request. 
Documentation could not be provided showing that all employees have reviewed and been training on the fire safety and evacuation plans. 
12/17/2015 
 

Sec. 605.4 2014 Edition IFC 675 IAC 22-2.5 
Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with NFPA 70 shall be prohibited. 
An unfused cube adapter was observed being used by the drink coolers with a drink cooler plugged into it. 
12/17/2015 
 

Sec. 605.5 2014 Edition IFC 675 IAC 22-2.5 
Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. 
An extension cord was found plugged in for permanent use and powering a sign above the drink coolers. 
 
 

Sec. 605.5.4 2014 Edition IFC 675 IAC 22-2.5 
Extension cords shall be grounded when serving grounded portable appliances. 
A grounded extension cord was found plugged into a non-grounded adapter located by the drink coolers behind the bar.