DHS

Indiana Department of Homeland Security / Fire and Building Safety Division

2020-21 version

 

Update Inspection

[Open Report in Chrome Browser]
[back to inspection list]
[view and Print Report (No Notes)]
[view and Print Report with Notes]
__________________________
Record Created Date: 09/22/2015
* facility ID:
* facility name:
* facility street number:
* facility street prefix:
* facility street name:
* facility street suffix:
facility address2:
* facility city:
* facility county:
facility state: IN
* facility zip:
* facility contact:
* facility telephone:
* facility Email:
Foundation/Footer status:
Concrete Slab status:
Framing Status:
Plumbing status:
Mechanical status:
Electrical status:
Energy status:
Sprinkler status:
alarm status:
sensitivity current :
Interior status:
Pool status:
Egress status:
Suppression status:
temporary indoor stage:
temporary outdoor stage:
outdoor stage equipment :
canopy:
tent :
ust installation:
ust removal:
project Type(select ll that apply): New: Addition: Remodel: Occ.Change: Existing:
inspection Category:
inspection type:
inspection status:
inspection Date: (mm/dd/yyyy)Pick a date
violation to be corrected by Date: (mm/dd/yyyy)Pick a date
* inspector:
notes:
Facility Match?: (Type in Facility Matched, when you match a complaint inspection with facility.)
[view & print annual permit] [Email permit]
print order code description remarks violation to be corrected by date violation complied date

Sec. 319.3.3 2014 Edition IFC 675 IAC 22-2.5 
A K-rated wet chemical fire extinguisher shall be provided where deep-fat fryers are used. 
"K" extinguishers missing in the following areas: 1.Funnel Cake booth, 2nd from end near Main & Perry, 2. Marks Concession Funnel Cake, 3. Amish Kuntry, 4. Deep Fried Candy Bars.  
10/24/2015 
 

Sec. 3103.12.3 2014 Edition IFC 675 IAC 22-2.5 
Exit openings from tents shall remain open unless covered by a flame-resistant curtain. The curtain shall comply with the following requirements: 1. Curtains shall be free sliding on a metal support.The support shall be a minimum of 80 inches (2032 mm) above the floor level at the exit. The curtains shall be so arranged that, when open, no part of the curtain obstructs the exit. 2. Curtains shall be of a color, or colors, that contrasts with the color of the tent. 
Any covering over openings shall meet these requirements. 
10/24/2015 
 

3103.12.2 2014 Edition IFC 675 IAC 22-2.5 
Tents, or membrane structures or a usable portion thereof shall have at least one exit and not less than the number of exits required by Table 3103.12.2. The total width of means of egress in inches (mm) shall not be less than the total occupant load served by a means of egress multiplied by 0.2 inches (5 mm) per person.  
Table shows that each exit shall be at least 72 inches in width. Partial blockage by junction boxes and exhibits are not allowed. Also tent stakes, barricades and such shall not be allowed. 
10/24/2015 
 

Sec. 319.2.5 2014 Edition IFC 675 IAC 22-2.5 
Electrical equipment and installations shall comply with the Indiana Electrical Code (675 IAC 17). 
Open junction boxes, incomplete wiring circuits, hanging electrical devices and such shall be corrected to bring them into compliance with the code. 
10/24/2015