DHS

Indiana Department of Homeland Security / Fire and Building Safety Division

2020-21 version

 

Update Inspection

[Open Report in Chrome Browser]
[back to inspection list]
[view and Print Report (No Notes)]
[view and Print Report with Notes]
__________________________
Record Created Date: 07/22/2015
* facility ID:
* facility name:
* facility street number:
* facility street prefix:
* facility street name:
* facility street suffix:
facility address2:
* facility city:
* facility county:
facility state: IN
* facility zip:
* facility contact:
* facility telephone:
* facility Email:
Foundation/Footer status:
Concrete Slab status:
Framing Status:
Plumbing status:
Mechanical status:
Electrical status:
Energy status:
Sprinkler status:
alarm status:
sensitivity current :
Interior status:
Pool status:
Egress status:
Suppression status:
temporary indoor stage:
temporary outdoor stage:
outdoor stage equipment :
canopy:
tent :
ust installation:
ust removal:
project Type(select ll that apply): New: Addition: Remodel: Occ.Change: Existing:
inspection Category:
inspection type:
inspection status:
inspection Date: (mm/dd/yyyy)Pick a date
violation to be corrected by Date: (mm/dd/yyyy)Pick a date
* inspector:
notes:
Facility Match?: (Type in Facility Matched, when you match a complaint inspection with facility.)
[view & print annual permit] [Email permit]
print order code description remarks violation to be corrected by date violation complied date

IC 22-14-3-5 
Operation without permit or special event endorsement; infraction Sec. 5. (a) This section applies to the following: (1) Each person who has control over the performance of an amusement or entertainment described in IC 22-12-1-23. (2) Each person who has control over a regulated place of entertainment. (b) A person described in subsection (a) commits a Class C infraction if: (1) a regulated place of amusement or entertainment is used for an amusement or entertainment described in IC 22-12-1-23; and (2) no regulated place of amusement or entertainment permit or special event endorsement issued under this chapter covers the conditions at the regulated place of amusement or entertainment that affect fire and explosion safety.  
Apply for and obtain state permit. 
07/23/2015 
 

Sec. 904.11 2014 Edition IFC 675 IAC 22-2.5 
The automatic fire-extinguishing system for commercial cooking systems shall be of a type recognized for protection of commercial cooking equipment and exhaust systems of the type and arrangement protected. Preengineered automatic dry- and wet-chemical extinguishing systems shall be tested in accordance with UL 300 and listed and labeled for the intended application. Other types of automatic fire-extinguishing systems shall be listed and labeled for specific use as protection for commercial cooking operations. The system shall be installed in accordance with this code, its listing and the manufacturer?s installation instructions. Automatic fire-extinguishing systems shall be installed in accordance with the Indiana Mechanical Code (675 IAC 18). Exception: Factory-built commercial cooking recirculating systems that are tested in accordance with UL 710B and listed, labeled and installed in accordance with Section 304.1 of the International Mechanical Code. 
Add additional heads for additional equipment. 
07/23/2015 
 

Sec. 609.3.3 2014 Edition IFC 675 IAC 22-2.5 
Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals as required by Sections 609.3.3.1 through 609.3.3.3. 
Clean hood, filters and ductwork. 
07/23/2015 
 

Sec. 904.11.6.2 2014 Edition IFC 675 IAC 22-2.5 
Automatic fire-extinguishing systems shall be serviced at least every six months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. 
Recertify overdue kitchen hood suppression system. 
07/23/2015 
 

Sec. 906.2 2014 Edition IFC 675 IAC 22-2.5 
Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. Exceptions: 1. The travel distance to reach an extinguisher shall not apply to the spectator seating portions of Group A-5 occupancies. 2. Thirty-day inspections shall not be required and maintenance shall be allowed to be once every three years for dry-chemical or halogenated agent portable fire extinguishers that are supervised by a listed and approved electronic monitoring device, provided that all of the following conditions are met: 2.1. Electronic monitoring shall confirm that extinguishers are properly positioned, properly charged and unobstructed. 2.2. Loss of power or circuit continuity to the electronic monitoring device shall initiate a trouble signal. 2.3. The extinguishers shall be installed inside of a building or cabinet in a noncorrosive environment. 2.4. Electronic monitoring devices and supervisory circuits shall be tested every three years when extinguisher maintenance is performed. 2.5. A written log of required hydrostatic test dates for extinguishers shall be maintained by the owner to verify that hydrostatic tests are conducted at the frequency required by NFPA 10. 3. In Group I-3, portable fire extinguishers shall be permitted to be located at staff locations. 
Recertify out of date extinguishers. 
07/23/2015 
07/22/2015 

Sec. 605.5 2014 Edition IFC 675 IAC 22-2.5 
Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. 
Remove ungrounded extension cord from family room TV and use power strip/surge protector. 
07/23/2015