DHS

Indiana Department of Homeland Security / Fire and Building Safety Division

2020-21 version

 

Update Inspection

[Open Report in Chrome Browser]
[back to inspection list]
[view and Print Report (No Notes)]
[view and Print Report with Notes]
__________________________
Record Created Date: 06/27/2014
* facility ID:
* facility name:
* facility street number:
* facility street prefix:
* facility street name:
* facility street suffix:
facility address2:
* facility city:
* facility county:
facility state: IN
* facility zip:
* facility contact:
* facility telephone:
* facility Email:
Foundation/Footer status:
Concrete Slab status:
Framing Status:
Plumbing status:
Mechanical status:
Electrical status:
Energy status:
Sprinkler status:
alarm status:
sensitivity current :
Interior status:
Pool status:
Egress status:
Suppression status:
temporary indoor stage:
temporary outdoor stage:
outdoor stage equipment :
canopy:
tent :
ust installation:
ust removal:
project Type(select ll that apply): New: Addition: Remodel: Occ.Change: Existing:
inspection Category:
inspection type:
inspection status:
inspection Date: (mm/dd/yyyy)Pick a date
violation to be corrected by Date: (mm/dd/yyyy)Pick a date
* inspector:
notes:
Facility Match?: (Type in Facility Matched, when you match a complaint inspection with facility.)
[view & print annual permit] [Email permit]
print order code description remarks violation to be corrected by date violation complied date

Sec. 605.6 2008 Edition IFC 675 IAC 22-2.4 
Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. 
The decorative lights above the "patio" are connected with an open splice. Also the wiriring is improperly supported.  
07/29/2014 
 

Sec. 1004.8 2008 Edition IFC 675 IAC 22-2.4  
Yards, patios, courts and similar outdoor areas accessible to and usable by the building occupants shall be provided with means of egress as required by this chapter. The occupant load of such outdoor areas shall be assigned by the building official in accordance with the anticipated use. Where outdoor areas are to be used by persons in addition to the occupants of the building, and the path of egress travel from the outdoor areas passes through the building, means of egress requirements for the building shall be based on the sum of the occupant loads of the building plus the outdoor areas. Exceptions: 1. Outdoor areas used exclusively for service of the building need only have one means of egress. 2. Both outdoor areas associated with Group R-3 and individual dwelling units of Group R-2. 
The patio exits back thru the building. A direct exit off of the patio is required 
07/29/2014 
 

Sec. 1008.1.8.3 2008 Edition IFC 675 IAC 22-2.4  
Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 1. Places of detention or restraint. 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: 2.1. The locking device is readily distinguishable as locked, 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, 3. Where egress doors are used in pairs, approved automatic flush bolts shall be permitted to be used, provided that the door leaf having the automatic flush bolts has no doorknob or surface-mounted hardware. 4. Doors from individual dwelling or sleeping units of Group R occupancies having an occupant load of 10 or less are permitted to be equipped with a night latch, dead bolt or security chain, provided such devices are openable from the inside without the use of a key or tool. 5. Licensed Health Care Facilities that comply with IC 22-11-17-2.  
The double cylinder locks on the main entrance are not readily distuinguishable as locked and no sign is posted.  
07/29/2014 
 

Sec. 1006.3 2008 Edition IFC 675 IAC 22-2.4  
The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the following areas: 1. Aisles and unenclosed egress stairways in rooms and spaces that require two or more means of egress. 2. Corridors, exit enclosures and exit passageways in buildings required to have two or more exits. 3. Exterior egress components at other than the level of exit discharge until exit discharge is accomplished for buildings required to have two or more exits. 4. Interior exit discharge elements, as permitted in Section 1024.1, in buildings required to have two or more exits. 5. Exterior landings, as required by Section 1008.1.5, for exit discharge doorways in buildings required to have two or more exits. The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702.  
Several of the Emergency egress lights are inoperable. 
07/29/2014 
 

Sec. 901.4.1 2008 Edition IFC 675 IAC 22-2.4 
Fire protection systems required by this code or the International Building Code shall be installed, repaired, operated, tested and maintained in accordance with this code. 
Alarms do not have a current test or maintainance report.  
07/29/2014